Plan Review Notes For Permit 04050070
Permit Number 04050070
Review Stop B
Sequence Number 3
Notes
Date Text
2004-10-08 00:00:00DENIED
  
 1) THE VALUES LISTED IN THE TABLE FOR
 THE USP THD28-2 CONNECTOR IN DETAIL 5 ON
 S2.03 ARE INCORRECT.
  
 2) THE STORM PANEL KEY/INSTALLATION
 SCHEDULE INDICATES STORM PANELS ON THE
 FRONT DOOR. THIS CONFLICTS WITH THE PLAN
 AND PRODUCT APPROVAL WHICH SPECIFY AN
 IMPACT RESISTANT GLAZED DOOR. PLEASE
 CORRECT.
  
 3) THE TRUSS LAYOUT AND DRAWINGS ARE
 REQUIRED TO BE REVIEWED AND APPROVED BY
 THE ARCHITECT. THEY ARE TO BE STAMPED
 AND SIGNED BY HIM AS BEING REVIEWED AND
 ACCEPTED.
  
 4) THE ROOF FRAMING PLAN ON S2.03 DOES
 NOT CLEARLY INDICATE THE UPLIFT AND
 CONNECTORS FOR THE ALL FOUR BEARING
 POINTS FOR TRUSSES A3, A4 AND A5. PLEASE
 CORRECT.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CALL:
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714