Plan Review Notes
Plan Review Notes For Permit 04050070
Permit Number 04050070
Review Stop E
Sequence Number 2
Notes
Date Text
2004-08-10 00:00:00*** UNSAT ***
  
 1)NOTE: PLEASE SEE OUTLETS FOR KITCHEN
 PENINSULAR/WALL AREA IS NOT CLEAR.
 PENINSULAR IS REQ'D TO GFI RECEPT PER
 210.52C3, PLEASE ALSO SEE (C5)
  
 2)NOTE: PLEASE SEE ADDED RECEPT FOR
 COND UNIT TO BE INDICATED AS WP/GFI.
 210.8 AS ON SYMBOL SCHEDULE.
  
 3)NOTE: PLEASE ALSO SEE RECEPT ADDED TO
 KITCHEN COUNTER, TO BE SHOWN AS GFI/
 GFI PROTECTED PER 210.8A6
  
 4)NOTE: PLEASE SEE OCP WAS CORRECTED FOR
 COND UNIT, HOWEVER LOAD IS SHOWN AT 10KW
 , PLEASE SEE IF LOAD OFR COND UNIT IS
 HIGHER THAN HEATING LOAD, THEN COND UNIT
 LOAD IS FIGNURED IN LOAD CALCS. THIS
 SEEMS TO BE A MISPRINT.
 2.5 TON CU LOAD IS MOST LIKELY NOT MORE
 THAN HEAT LOAD. PLEASE VERIFY.
  
 5)NOTE: PLEASE SEE GENERAL NOTES, NOTE
 #3 LAST LINE STILL MENTIONS ARC-FAULT
 FOR RECEPTS. PLEASE REMOVE DUE TO NEW
 NOTE BEING ADDED BELOW THIS.
  
 PLEASE NOTE: THESE PLANS ARE ONLY IN FOR
 "PLAN REVIEW" FOR A MASTER. THIS REQUIRE
 'S EVERY ITEM TO BE 100% CORRECT AND
 NO REDLINES CAN BE DONE.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]