| 2004-08-10 00:00:00 | *** UNSAT *** |
| | |
| | 1)NOTE: PLEASE SEE OUTLETS FOR KITCHEN |
| | PENINSULAR/WALL AREA IS NOT CLEAR. |
| | PENINSULAR IS REQ'D TO GFI RECEPT PER |
| | 210.52C3, PLEASE ALSO SEE (C5) |
| | |
| | 2)NOTE: PLEASE SEE ADDED RECEPT FOR |
| | COND UNIT TO BE INDICATED AS WP/GFI. |
| | 210.8 AS ON SYMBOL SCHEDULE. |
| | |
| | 3)NOTE: PLEASE ALSO SEE RECEPT ADDED TO |
| | KITCHEN COUNTER, TO BE SHOWN AS GFI/ |
| | GFI PROTECTED PER 210.8A6 |
| | |
| | 4)NOTE: PLEASE SEE OCP WAS CORRECTED FOR |
| | COND UNIT, HOWEVER LOAD IS SHOWN AT 10KW |
| | , PLEASE SEE IF LOAD OFR COND UNIT IS |
| | HIGHER THAN HEATING LOAD, THEN COND UNIT |
| | LOAD IS FIGNURED IN LOAD CALCS. THIS |
| | SEEMS TO BE A MISPRINT. |
| | 2.5 TON CU LOAD IS MOST LIKELY NOT MORE |
| | THAN HEAT LOAD. PLEASE VERIFY. |
| | |
| | 5)NOTE: PLEASE SEE GENERAL NOTES, NOTE |
| | #3 LAST LINE STILL MENTIONS ARC-FAULT |
| | FOR RECEPTS. PLEASE REMOVE DUE TO NEW |
| | NOTE BEING ADDED BELOW THIS. |
| | |
| | PLEASE NOTE: THESE PLANS ARE ONLY IN FOR |
| | "PLAN REVIEW" FOR A MASTER. THIS REQUIRE |
| | 'S EVERY ITEM TO BE 100% CORRECT AND |
| | NO REDLINES CAN BE DONE. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |