| Date |
Text |
| 2004-05-10 00:00:00 | ********* UNSAT *********** |
| | |
| | 1)NOTE: PLEASE SEE 210.52 FOR RECEPT |
| | SPACING IN BED RM #1, 2',6'12' RULE. |
| | 6' OF DR. |
| | |
| | 2)NOTE: PLEASE SEE MISSING EQUIPMENT |
| | GROUNDING CONDUCTOR FROM MAIN TO PANEL. |
| | 250.110, SIZE PER 250.122 |
| | |
| | 3)NOTE: PLEASE SEE ALL RECEPTS OUTSIDE |
| | TO BE SHOWN AS GFI/GFI PROTECTED. |
| | 210.8 |
| | |
| | 4)NOTE: PLEASE SHOW DISC FOR COND UNIT |
| | PER 110.26. DISC SHOWN BEHIND UNIT. |
| | |
| | 5)NOTE: PLEASE SEE RISER SHOWS A MAIN |
| | DISCONNECT, HOWEVER MAIN IS NOT SHOWN |
| | ON PLANS NEXT TO METER. PLEASE SHOW. |
| | |
| | 6)NOTE : PLEASE SEE PANEL SCHEDULE |
| | INDICATES PANEL BEING MCB? PLEASE SEE |
| | RISER SHOWS A MAIN ON OUTSIDE ALSO. |
| | THIS IS PRMITTED,HOWEVER IF SHOWN ON |
| | PLANS THEN IT WOULD BE REQ'D TO BE |
| | INSTALLED. |
| | PLEASE ALSO SEE PANEL IS SHOWN AT 42CIR |
| | PLEASE VERIFY THIS # OF CIRCUITS FOR |
| | A 150A PANEL. PANEL SHOWS 42 AND RISER |
| | 36. |
| | |
| | 7)NOTE: PLEASE SEE SOME FIXTURES SHOWN |
| | ON PLANS DO NOT SEEM TO CORRELATE WITH |
| | FIXTURE SCHEDULE? |
| | PLEASE SEE 220.3B4. |
| | PLEASE SHOW ALL RECESSED LTS BASED ON |
| | MAX WATTAGE FOR FIXTURE(S). THIS MAY NOT |
| | BE FIGURED IN W/ 3W/PER SQ FT. |
| | PLEASE PROVIDE FIXTURE INFORMATION ON |
| | LEGEND. |
| | |
| | 8)NOTE: ARC FAULT IS NOTED PER 210.12B, |
| | PLEASE INDICATE 2002 NEC/ ALL OUTLETS. |
| | |
| | 9)NOTE: PLEASE SEE OCP FOR 2.5 TON CU. |
| | SHOWN AS 60A W/ #6'S. THIS SEEMS TO BE |
| | TOO HIGH FOR OCP. |
| | |
| | PLEASE SEE ON SET OF PLANS HAS REDLINES |
| | |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CITY OF WEST PALM BEACH |
| | CONSTUCTION SERVICES DEPT. |
| | 561-805-6717 |
| | [email protected] |