Plan Review Notes
Plan Review Notes For Permit 04050070
Permit Number 04050070
Review Stop B
Sequence Number 1
Notes
Date Text
2004-06-03 00:00:00DENIED
  
 1) SUBMIT TRUSS DRAWINGS AND LAYOUT THAT
 HAVE BEEN REVIEWED AND APPROVED BY THE
 DESIGNER OF RECORD.
  
 2) THE ENERGY CALCS ARE REQUIRED TO BE
 WORST CASE FOR THE MODEL. THE FORM IS
 REQUIRED TO BE SIGNED AND DATED BY THE
 OWNER AGENT. THE CONDITIONED FLOOR AREA
 ON THE FORM AND THE PLANS SHOULD BE THE
 SAME.
  
 3) SPECIFY THE BOTTOM CORD LIVE LOAD ON
 THE PLANS. SEE 2001 FBC TABLE 1604.1.
  
 4) THE FLOOR PLAN ON A2.01 DOES NOT
 CORRESPOND WITH THE REST OF THE PLANS.
 SEE SOUTH ELEVATION AT BEDROOM 3.
  
 5) THE FOOTING SHOWN IN THE WALL SECTION
 ON S2.01 DOES NOT CORRESPOND WITH THE
 FOOTING SCHEDULE. PLEASE CORRECT.
  
 6) THE ISOLATED PAD DETAIL ON S2.01 IS
 INCORRECTLY LABELED AS 7. IT SHOULD BE
 4.
  
 7) THE TRUSS CONNECTOR IN THE WALL
 SECTION ON S2.01 SHOULD BE USP.
  
 8) SPECIFY THE MATERIAL USED FOR THE
 CEILINGS (DIAPHRAGM) OF THE COVERED
 PORCHES.
  
 9) SUBMIT STATE PRODUCT APPROVALS FOR
 THE USP CONNECTORS.
  
 10) THE USP THD28-2 HAS A MAXIMUM UPLIFT
 OF 2390# AT 133% PER 2004 USP CATALOG.
 PLEASE REVISE DETAIL 5 ON S2.03.
  
 11)THE UPLIFT FOR THE ROOF TRUSS GIRDERS
 AT THE LEFT SIDE ARE NOT SPECIFIED OR
 ARE INCORRECT. SEE NOTES ON PLAN.
  
 12) THE EXTERIOR WALLS AT THE REAR PORCH
 ARE NOT SHOWN ON THE ROOF FRAMING PLAN
 ON S2.03.
  
 13) ON S3.01 THE WALL SHEATHING IS
 SPECIFIED AS 15/32" IN ONE PLACE AND
 5/8" IN ANOTHER. PLEASE CLARIFY.
  
 14) THE ROOF SHEATHING IS INCORRECTLY
 SPECIFIED AS 15/32" ON SHEET S3.01. CITY
 OF WPB AMENDMENTS TO FBC TABLE 2309.3A
 REQUIRES SHEATHING TO BE A MINIMUM OF
 19/32".
  
 15) CITY AMENDMENTS TO FBC TABLE 2306.1
 REQUIRES ROOF SHEATHING TO BE NAILED AT
 4"OC ON THE EDGES AND 6"OC INTERMEDIATE
 IN ZONE 3, WHICH INCLUDES THE COORNERS
 OF HIP ROOFS. PLEASE REVISE NOTES ON
 S3.01.
  
 16) PLEASE UPDATE THE ACI EDITIONS THAT
 ARE SPECIFIED ON S3.01 TO 2002 EDITIONS
 AS REFERENCED BY THE 2001 FBC CHAPTER 35
 SEE NOTES ON THE PLANS.
  
 17) SUBMIT A KEY PLAN AND INSTALLATION
 SCHEDULE FOR THE STORM PANELS. SPECIFY
 THE INSTALLATION TYPE AND FASTENERS THAT
 WILL BE USED BY CIRCLING OR HIGHLIGHTING
 APPROPRIATE ITEMS ON THE INSTALLATION
 DRAWINGS.
  
 18) SUBMIT STATE PRODUCT APPROVALS FOR
 THE FOLLOWING ITEMS:
 - SINGLE OUTSWING DOOR AT KITCHEN
 - DOUBLE OUTSWING DOOR AT STORAGE
 - ALUMINUM SOFFIT
 - TRUSS CONNECTORS
  
 19) ONE OF THE PRODUCT APPROVALS FOR THE
 STORM PANELS IS MISSING THE INSTALLATION
 DRAWINGS.
  
 THE FOLLOWING ITEMS WILL BE REQUIRED TO
 BE SUBMITTED FOR EACH PERMIT APPLICATION
 UNDER THE MASTER.
 - NOTICE OF COMMENCEMENT
 - PAID RECEIPT FOR COUNTY IMPACT FEES
 AND PLANS STAMPED BY THE COUNTY
 - TWO COPIES OF SURVEY
 - TWO COPIES OF SUBSURFACE SOIL REPORT
 PER FBC 1804.2.2
  
 IF YOU HAVE QUESTIONS PLEASE CALL:
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714