| Plan Review Notes For Permit 04050061 |
| Permit Number |
04050061 |
|
| Review Stop |
E |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2004-06-22 00:00:00 | ************** UNSAT *************** | | | | | | PLEASE SEE PLANS ARE NOW COMING BACK IN | | | SHOWING AN EXISTING SERVICE FOR REMODEL. | | | | | | 1)NOTE: PLEASE CORRELATE RISER, PANEL | | | AND NOTES. | | | RISER SHOWS PANELS AS MCB, PANEL SHOWN | | | AS MLO AND CURRENT LIMITED FUSES?? | | | | | | 2)NOTE: PLEASE SEE 210.11C1, A MIN OF | | | TWO SMALL APPLIANCE CIRCUITS REQ'D AND | | | EACH TO BE AMIN OF 1500VA. SHOWS ONE' | | | FOR EACH AND ALSO SHOWS LOAD AT 600 VA | | | EACH. 210.52B | | | | | | 3)NOTE: PLEASE SEE 220.16, A MIN OF | | | 1500 VA TO BE FIGURED FOR REQUIRED | | | WASHER CIRCUIT FOR EACH UNIT. | | | | | | 4)NOTE: PLEASE VERIFY, PANEL SCHEDULES | | | INDICATE ONE OVEN AND ONE RANGE IN EACH | | | UNIT. PLEASE SEE PLANS, RANGE SHOWN AT | | | 8KW WHICH IS MIN AND AN OVEN SEPARATE | | | @ 6KW?PLANS ONLY SHOW ONE IN EACH | | | UNIT. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE TO CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CITY OF WEST PALM BEACH | | | CONSTUCTION SERVICES DEPT. | | | 561-805-6717 | | | [email protected] |
|