Plan Review Notes
Plan Review Notes For Permit 04050061
Permit Number 04050061
Review Stop E
Sequence Number 1
Notes
Date Text
2004-05-08 00:00:00*************** UNSAT ************
  
 1)NOTE: PLEASE SUBMIT PANEL SCHEDULE(S)
 SHOWING ALL MIN CIRCUITING PER 2002 NEC
  
 2) NOTE: PLEASE SHOW ALL RECEPTS SERVING
 KITCHEN COUNTERSPACE AS GFI/GFI PROTECT-
 -ED PER 210.8A-6
 PLEASE ALSO SEE 210.52 C1,2,3,4,5, FOR
 RECEPT SPACING.
  
 3) NOTE: SMOKE DETECTORS ARE REQUIRED
 INSIDE AND OUTSIDE ALL SLEEPING ROOMS.
 ON EACH LEVEL OF A MULTI-LEVEL DWELLING
 UNIT.
 PLEASE ALSO NOTE, SD'S ARE REQ'D TO BE
 A MIN OF 3' FROM BATHROOM DOORS AND
 KITCHENS.
 ABOVE PER:FBC 905.2, NFPA-72 8-1.4
 8-1.4.2.
  
 4 )NOTE: PLEASE SEE MISSING REQ'D EGRESS
 LIGHTING AND/OR CLARIFY EGRESS LIGHTING
 PER 210.70 AND LS-101 5-8
 PLEASE SEE FIRST FLR, STAIRS? PHOTOCELL?
 3-WAY CONTROL?
 PLEASE ALSO SEE EGRESS FROM LOWER FLR.
  
 5 ) NOTE: PLEASE SEE MISSING RECEPTS FOR
 FRONT AND/OR REAR OF DWELLING.
 210.52E
  
 6)NOTE: PLEASE SHOW ANY A/C SYSTEMS,
 UNITS, DISC 440.11, RECEPTS 210.63
  
 7)NOTE: PLEASE SEE FS 481.221, ARCH
 MUST ALSO SIGN FIRST NAME. INITIAL FOR
 FIRST NAME IS NOT PERMITTED PER FS ,
 FAC ,DBPR.
  
 8 )NOTE: PLEASE LIST THE REQ'D ARC
 FAULT PROTECTED CURCUIT(S) ON PANEL
 SCHEDULE. PLEASE SEE THAT ALL "OUTLETS"
 IN BEDROOMS ARE TO BE PROTECTED ,
 INCLUDING, LTS, RECEPTS, SD'S ETC.
 210.12
  
 PLEASE SEE , ALL INFORMATION NEEDED WAS
 NOT SUBMITTED AT THIS TIME. UNABLE TO
 DO COMPLETE REVIEW FOR CODE COMPLIANCE.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]