| 2004-05-08 00:00:00 | *************** UNSAT ************ |
| | |
| | 1)NOTE: PLEASE SUBMIT PANEL SCHEDULE(S) |
| | SHOWING ALL MIN CIRCUITING PER 2002 NEC |
| | |
| | 2) NOTE: PLEASE SHOW ALL RECEPTS SERVING |
| | KITCHEN COUNTERSPACE AS GFI/GFI PROTECT- |
| | -ED PER 210.8A-6 |
| | PLEASE ALSO SEE 210.52 C1,2,3,4,5, FOR |
| | RECEPT SPACING. |
| | |
| | 3) NOTE: SMOKE DETECTORS ARE REQUIRED |
| | INSIDE AND OUTSIDE ALL SLEEPING ROOMS. |
| | ON EACH LEVEL OF A MULTI-LEVEL DWELLING |
| | UNIT. |
| | PLEASE ALSO NOTE, SD'S ARE REQ'D TO BE |
| | A MIN OF 3' FROM BATHROOM DOORS AND |
| | KITCHENS. |
| | ABOVE PER:FBC 905.2, NFPA-72 8-1.4 |
| | 8-1.4.2. |
| | |
| | 4 )NOTE: PLEASE SEE MISSING REQ'D EGRESS |
| | LIGHTING AND/OR CLARIFY EGRESS LIGHTING |
| | PER 210.70 AND LS-101 5-8 |
| | PLEASE SEE FIRST FLR, STAIRS? PHOTOCELL? |
| | 3-WAY CONTROL? |
| | PLEASE ALSO SEE EGRESS FROM LOWER FLR. |
| | |
| | 5 ) NOTE: PLEASE SEE MISSING RECEPTS FOR |
| | FRONT AND/OR REAR OF DWELLING. |
| | 210.52E |
| | |
| | 6)NOTE: PLEASE SHOW ANY A/C SYSTEMS, |
| | UNITS, DISC 440.11, RECEPTS 210.63 |
| | |
| | 7)NOTE: PLEASE SEE FS 481.221, ARCH |
| | MUST ALSO SIGN FIRST NAME. INITIAL FOR |
| | FIRST NAME IS NOT PERMITTED PER FS , |
| | FAC ,DBPR. |
| | |
| | 8 )NOTE: PLEASE LIST THE REQ'D ARC |
| | FAULT PROTECTED CURCUIT(S) ON PANEL |
| | SCHEDULE. PLEASE SEE THAT ALL "OUTLETS" |
| | IN BEDROOMS ARE TO BE PROTECTED , |
| | INCLUDING, LTS, RECEPTS, SD'S ETC. |
| | 210.12 |
| | |
| | PLEASE SEE , ALL INFORMATION NEEDED WAS |
| | NOT SUBMITTED AT THIS TIME. UNABLE TO |
| | DO COMPLETE REVIEW FOR CODE COMPLIANCE. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |