Notes
Date Text
2004-05-13 00:00:00PROVISO:
 PLAN INDICATES 2 OF THE BEDROOMS WITH
 THE SUPPLY AIR AS 200 CFM, THE RETURN
 AIR GRILLES SHALL BE NO LESS THAN 100
 SQ INCHES OF GRILLE AREA (12" X 8" = 96
 SQ INCHES).PLEASE REVISE PLAN
 ACCORDINGLY.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.