| Plan Review Notes For Permit 04042064 |
| Permit Number |
04042064 |
|
| Review Stop |
M |
| Sequence Number |
5 |
|
| Notes |
| Date |
Text |
| 2006-03-22 00:00:00 | *** DENIED *** | | | 1) AHU'S 1&2 SUPPLY AIR DUCTS (30"X5") | | | APPEARS TO SMALL FOR A 4 TON AND A 3 TON | | | SYSTEM. PLEASE SUBMIT A MANUAL J FOR ALL | | | UNITS SHOWING CFM'S AND DUCT SIZES, PER | | | 2004 FBC/R M1401.3 . | | | | | | 2) AHU #4 SUPPLY AIR DUCT TO THE MASTER | | | SUITE IS 14" AND THE RETURN AIR DUCT IS | | | 12" TO ACHIEVE A BALANCE RETURN TI NEEDS | | | TO BE 14" PLEASE CORRECT, PER 2004 FBC/R | | | M1602.4 . | | | | | | 3) ELECTRIAL PLANS ARE SHOWING A GAS | | | WATER HEATER ON THE SECOND FLOOR | | | DRESSING ROOM CLOSET. PLEASE PROVIDE | | | COMBUSTION AIR AND COMBUSTION AIR | | | CALCULATIONS ON MECHANICAL PLANS, OR IF | | | THERE IS NO WATER HEATER HAVE ELECT. | | | PLANS CORRECTED. | | | | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729. | | | |
|