| | PLEASE MAKE THE FOLLOWING CORRECTIONS |
| | FOR CODE COMPLIANCE AND RESUBMIT FOR |
| | REVIEW. |
| | |
| | |
| | THESE ITEMS WERE REDLINED ON PREVIOUS |
| | PLANS AND NOT CORRECTED ON REVISIONS. |
| | |
| | 1} THE GROUNDING ELECTRODE CONDUCTOR IS |
| | NOT SUFFICIENT FOR THE SIZE OF THE |
| | SERVICE. THE SMALLEST ALLOWABLE FOR 400 |
| | MCM FEEDERS IS #1/0CU PER 250.66. TWO |
| | CONDUCTORS CAN NOT BE SUBSTITUTED FOR |
| | THE SINGLE CONDUCTOR REQUIREMENT AS THEY |
| | CREATE PARALLEL GROUNDING PATHS.SEE |
| | 250.6. |
| | |
| | 2} SEE 250.50 FOR GROUNDING REQUIREMENTS |
| | INCLUDING FOOTER STEEL. LIST ALL |
| | AVAILABLE TO BE BONDED TOGETHER ON THE |
| | RISER DIAGRAM. |
| | |
| | 3} THE RECEPTACLES ON THE PORTICO MUST |
| | BE GFI PER 210.8(A)(3). INDICATE SAME ON |
| | PLANS. |
| | |
| | THESE CORRECTIONS ARE DUE TO THE |
| | REVISION. |
| | |
| | 1} SMOKE DETECTORS ARE REQUIRED AT THE |
| | STAIRS PER 905.2.2 FBC. |
| | |
| | 2} SMOKE DETECTORS ARE REQUIRED INSIDE |
| | AND OUTSIDE BEDROOM #4 PER 8-1.4.1.6.2 |
| | NFPA-72. |
| | |
| | 3} THE VALUE OF THE PROJECT MUST BE |
| | INCREASED TO REFLECT ADDED SQUARE |
| | FOOTAGE. PLEASE NOTE SAME TO PERMIT |
| | SPECIALIST AT THE TIME OF RESUBMITTAL. |
| | |
| | PLEASE NOTE ALL KITCHEN COUNTERTOP |
| | RECEPTACLES MUST BE GFI PROTECTED PER |
| | 210.8(A)(6). SEE COUNTERTOPS BETWEEN THE |
| | REFRIGERATOR'S. |
| | |
| | ALSO NOTE THE 250MCM CONDUCTORS FEEDING |
| | THE 200 AMP PANELS ARE OVERSIZED. |
| | ALTHOUGH NOT A VIOLATION IF THEY FIT |
| | UNDER THE LUGS, THEY MUST BE INSTALLED |
| | IF LEFT ON REVIEWED PLANS. |
| | |
| | IF THERE ARE ANY QUESTIONS PLEASE CALL. |
| | |