| 2004-05-11 00:00:00 | |
| | PLEASE MAKE THE FOLLOWING CORRECTIONS |
| | FOR CODE COMPLIANCE AND RESUBMIT FOR |
| | REVIEW. |
| | |
| | 1} PLEASE SUBMIT AIC RATINGS FOR |
| | ALL NEW SERVICE EQUIPMENT BEING |
| | INSTALLED. MAINS/BRKRS AND PANELS ARE |
| | ALL TO BE RATED FOR THE AVAILABLE FAULT |
| | CURRENT. |
| | PER 110.9/215.5 |
| | |
| | 2} THE GROUNDING ELECTRODE CONDUCTOR IS |
| | UNDERSIZED PER 250.66. |
| | |
| | 3} THE GROUNDING ELECTRODE SYSTEM MUST |
| | BE INSTALLED PER 250.50, ALL ITEMS |
| | AVAILABLE MUST BE USED. PLEASE NOTE |
| | SAME ON PLANS. |
| | |
| | 4} THE SERVICE CONDUCTORS @ 250 MCM ARE |
| | UNDERSIZED FOR THE 400 AMP OCP MAIN. |
| | SEE 310.15(B)(6).(400 MCM). |
| | |
| | 5} PLEASE LIST ALL THE REQUIRED |
| | DEDICATED BATH(S) CIRCUIT(S) ON PANEL |
| | SCHEDULE PER 210.11C3. |
| | |
| | 6} PLEASE LIST THE REQUIRED ARC |
| | FAULT PROTECTED CIRCUIT(S) ON PANEL |
| | SCHEDULE. PLEASE SEE THAT ALL "OUTLETS" |
| | IN BEDROOMS ARE TO BE PROTECTED , |
| | INCLUDING, LTS, RECEPTS, SD'S ETC. |
| | |
| | 7} THE FOLLOWING APPLIANCE CIRCUITS |
| | MUST BE CALCULATED AS INDICATED. |
| | A) LAUNDRY PER 210.16(B)-1500VA. |
| | B) DRYER PER 210.18-5000VA. |
| | C) SMALL APPLIANCE 220.16(A)-1500 EA. |
| | |
| | 8} PLEASE PROVIDE A PANEL SCHEDULE SO |
| | THAT CODE COMPLIANCE OF CIRCUITING CAN |
| | BE DETERMINED. |
| | |
| | 9} A SMOKE DETECTOR MUST BE ADDED AT THE |
| | STAIRWELL ON THE FIRST FLOOR TO COMPLY |
| | WITH 905.2.2 F.B.C.. |
| | |
| | 10} THE ELEVATOR EQUIPMENT IS NOT LISTED |
| | IN THE LOAD CALCULATION. |
| | |
| | 11} THE DISPOSAL IS NOT LISTED IN THE |
| | CALCULATION. |
| | |
| | 12} THE GARAGE RECEPTACLES MUST COMPLY |
| | WITH 210.8(A)(2). |
| | |
| | 13} THE RECEPTACLES ON THE PORTICO MUST |
| | BE GFI PER 210.8(A)(3),GFI. |
| | |
| | 14} ALL OF THE OUTDOOR EQUIPMENT |
| | DISCONNECTS MUST COMPLY WITH 110.26 |
| | CLEARANCE. |
| | |
| | 15} THE PHONE NUMBER OF THE ARCHITECT |
| | MUST BE CONTAINED IN THE TITLE BLOCK |
| | PER 61G1-16.004(2) FAC. |
| | |
| | THE AREAS OF NON COMPLIANCE ARE NOTED ON |
| | ONE SET OF REVIEWED PLANS TO AID THE |
| | ARCHITECT IN MAKING CORRECTIONS. IF |
| | THERE ARE ANY QUESTIONS PLEASE CALL. |
| | |