| Notes |
| Date |
Text |
| 2007-01-16 10:22:01 | ***DENIED*** | | | | | | 1) FIRE EXTINGUISHERS ARE SHOWN ON SOME SHEETS, BUT | | | MISSING ON OTHERS. WHEN THE LOCATIONS ARE ILLUSTRATED, | | | PLACEMENT SHALL BE WITHIN 75' TRAVEL DISTANCE. | | | | | | 2) NEW FIRE DAMPER INSTALLATIONS SHALL BE TESTED FOR | | | CLOSURE PRIOR TO FINAL INSPECTION. | | | | | | 3) IF SEPARATE SHOP DRAWINGS AND PERMIT HAS BEEN ISSUED | | | FOR FIRE ALARM SYSTEM, CHANGES TO THAT SYSTEM TO BE | | | SUBMITTED UNDER THAT PERMIT. | | | | | | 4) SOME SMOKE DETECTORS APPEAR TO BE MISSING FROM | | | ELEVATOR LOBBIES. | | | | | | | | | MIKE WENNERGREN, ASSISTANT FIRE MARSHAL | | | FIRE PLAN REVIEW | | | (561) 805-6722 OR 804-4756 |
|