| Plan Review Notes For Permit 04042022 |
| Permit Number |
04042022 |
|
| Review Stop |
FIRE |
| Sequence Number |
6 |
|
| Notes |
| Date |
Text |
| 2006-01-04 00:00:00 | 1. THE PROPOSED SIXTH FLOOR ADDITION TO | | | THE GARAGE SHALL COMPLY WITH NFPA 88A. | | | | | | 2. EXIT STAIRS SHALL COMPLY WITH ALL NEW | | | STAIR REQUIREMENTS. | | | | | | 3. SIGNS ARE REQUIRED INDICATING STAIR | | | IDENTITY, FLOOR LEVEL, STAIR TERMINUS | | | TOP AND BOTTOM, ETC. | | | | | | 4. EXIT SIGNS ON THE 6TH FLOOR LEVEL | | | SHALL NOT EXCEED 100 FEET. | | | | | | 5. EMERGENCY LIGHTING ON THE 6TH FLOOR | | | LEVEL SHALL MEET MINIMUM CODE | | | REQUIREMENTS. | | | | | | MIKE CARSILLO, CHIEF FIRE PREVENTION | | | OFFICER | | | 804-4709 |
|