| 2005-03-12 00:00:00 | DENIED |
| | REFERENCE: FBC-2001 PLUMBING |
| | FBC-2001 CHAPTER 1 |
| | FLORIDA ADMINISTRATIVE CODE |
| | FLORIDA STATUTES |
| | |
| | A) FROM PREVIOUS REVIEW: COMMENT NUMBERS |
| | SHALL STAY THE SAME TO AVOID CONFUSION. |
| | 1) A TITLE BLOCK MUST APPEAR ON ALL |
| | ARCHITECTURAL DRAWINGS AND SPECIFICATION |
| | IDENTIFICATION SHEETS. THE TITLE BLOCK |
| | MUST, AT A MINIMUM, CONTAIN THE |
| | FOLLOWING INFORMATION: |
| | (1) FIRM NAME, ADDRESS, AND TELEPHONE |
| | NUMBER. |
| | IF THE FIRM NAME IS A CORP., PARTNERSHIP |
| | OR A FICITIOUS NAME A CERTIFICATE OF |
| | AUTHORIZATION IS REQUIRED. 61G1-16.004 & |
| | FS 481.219 FS 481.2055 - NO RESPONSE |
| | NOTED. |
| | 3) DRINKING FOUNTAINS ARE REQUIRED PER |
| | TABLE 403.1. RESPONSE NOTED, BUT IF THIS |
| | IS A NEW BUILDING THEN HOW CAN THERE BE |
| | EXISTING DRINKING FOUNTAINS? NO DRINKING |
| | FOUNTAINS ARE SHOWN ON THE FLOOR PLAN OR |
| | THE SANT. RISER DIAGRAM. |
| | 4) CONTACT RODNEY COMPO, ENVIRONMENTAL |
| | COMPLIANCE FOR GREASE INTERCEPTOR. WASTE |
| | ORD #2938-96. (561) 837-4074. RESPONSE |
| | NOTED, BUT THIS IS NOT A PERMIT ISSUE. |
| | THIS IS TO SEE IF A GREASE INTERCEPTOR |
| | WILL BE REQUIRED, AND IF ONE IS A GREASE |
| | LINE CAN BE BROUGHT INTO THE BUILDING |
| | NOW RATHER THAN TEARING UP THE FLOOR IN |
| | THE FUTURE. |
| | *********NEW COMMENTS SOME BECAUSE OF |
| | CHANGES IN THE PLANS OR NEW SHEETS****** |
| | 1B) SHT P2.1 LABELED AS SANITARY, BUT |
| | HAS STORM AND CONDENSATE ALSO. - STORM |
| | LINE AT COL. LINE B?X9 DOES NOT REFLECT |
| | THE RISER ON SHT P7.1. RISER DIAGRAM |
| | SHOWS 2 STORM RISERS, BUT FLOOR PLAN |
| | SHOWS ONLY ONE. PLEASE CORRELATE FLOOR |
| | PLAN AND RISER DIAGRAM. |
| | 2B) SHTS P2.1A & P5.1 FLOOR DRAIN IN |
| | PUMP NOT VENTED. SECTION 901.2.1. |
| | 3B) SHTS P2.1A & P5.1 PIPING UPSTREAM OF |
| | THE PUMP ROOM FLOOR DRAINS, THE FLOOR |
| | PLAN AND RISER DIAGRAM DO NOT REFLECT |
| | EACH OTHER. FLOOR PLAN SHOWS 6" PIPING |
| | AND THE RISER DIAGRAM SHOWS 8" PLEASE |
| | CORRELATE. SECTION 104.2.1. |
| | 4B) SHTS P2.1A & P5.1 SANT. RISER |
| | DIAGRAM DOES NOT REFLECT THE FLOOR PLAN. |
| | THE COFFEE SHOP IN NOT ON THE RISER |
| | DIAGRAM. PLEASE CORRELATE. SECTION |
| | 104.2.1. |
| | 5B) SHTS P2.1B & P5.1 SANT. RISER |
| | DIAGRAM DOES NOT REFLECT THE FLOOR PLAN. |
| | SANT. RISER DIAGRAM SHOWS 4" TO THE |
| | TICKED BOOTH AND THE FLOOR PLAN SHOWS |
| | 6". PLEASE CLARIFY. SECTION 104.2.1. |
| | 6B) SHTS P2.2B, P2.3B SHOW STORM DRAINS |
| | AS FLOOR DRAINS ON THE FLOOR PLAN, BUT |
| | ARE SHOWN AS DECK DRAINS ON THE STORM |
| | RISER SHT P7.1. PLEASE CORRELATE/CLARIFY |
| | SECTION 104.2.1. |
| | 7B) SHTS P2.2B, P2.3B, P2.4B & P2.5B ARE |
| | LABELED AS SANITARY FLOOR PLANS, BUT THE |
| | INFORMATION IS FOR STORM DRAINAGE. |
| | PLEASE CLARIFY. SECTION 104.2.1. |
| | 8B) SHTS P2.5B & P7.1 DO NOT REFLECT |
| | EACH OTHER. STORM RISER DIAGRAM DOES NOT |
| | SHOW 2" PLANTER DRAIN LINE. PLEASE |
| | CORRELATE SHEETS. SECTION 104.2.1. |
| | 9B) SHT P5.1 STACKS FOR LAVS NOT SIZED |
| | CORRECTLY. MAXIMUM 10 DFU'S ON 2" STACK |
| | WITH 3 BRANCH INTERVALS OR LESS. 18 DFU |
| | SHOWN. TABLE 710.1(2). |
| | 10B) SHTS P3.19 & P6.1 FULL OPEN VALVES |
| | REQUIRED ON THE WATER DISTRIBUTION |
| | SUPPLY PIPE AT THE ENTRANCE INTO THE |
| | STRUCTURE, SECTION 606.1(2), AND ON THE |
| | TOP OF EVERY WATER DOWN-FEED PIPE, |
| | SECTION 606.1(4). |
| | 11B) SHT P6.1 WATER LINE TO TICKET BOOTH |
| | NOT SHOWN ON THE WATER RISER DIAGRAM. - |
| | WATER LINE BY COL. X7 NOT SHOWN ON THE |
| | WATER RISER DIAGRAM. -DOES NOT REFLECT |
| | THE WATER PIPING SHOWN ON SHT P3.1A BY |
| | COL. LINES B/X1!!! THRU A"/X1. |
| | |
| | REVIEW BY KEN STEVENS |