| Plan Review Notes For Permit 04042022 |
| Permit Number |
04042022 |
|
| Review Stop |
E |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2005-03-10 00:00:00 | | | | PLEASE MAKE THE FOLLOWING CORRECTIONS | | | FOR CODE COMPLIANCE AND RESUBMIT FOR | | | REVIEW. | | | | | | 1} INDICATE THE FIRE PUMP MOTER DESIGN | | | LETTER SO THAT LOCKEE ROTOR CURRENT CAN | | | BE DETERMINED FOR THE DISCONNECTING | | | MEANS. I COULD NOT FIND THE DESIGNATION | | | IN THE SPECS. | | | | | | 2} INDICATE THAT THE FIRE PUMP | | | CONTROLLER HAS AN EXTERNAL MEANS OF | | | DISCONNECT ON THE PLAN ALSO INDICATE | | | AMPERAGE RATING OF SAME ON PLANS. AGAIN | | | THESE WERE NOT CLEAR IN THE SPECS. | | | | | | 3} CORRELATE THE HP OF THE FIRE PUMP | | | RATING ON THE PLAN WITH THE ONE IN THE | | | SPECS. | | | | | | 4} THERE ARE STILL NO LOAD OR BREAKER | | | SIZES IN MSBA FOR CIRCUITS 7,8&9. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 | | | [email protected] | | | FAX/:561/659-8026 | | | | | | |
|