| 2004-09-16 00:00:00 | 1) NO EXIT SIGN OR EMERGENCY LIGHTS IN |
| | CAFE OR BANK. |
| | |
| | 2) AN EXIT SIGN ON THE FIRST FLOOR |
| | LIGHTING PLAN DIRECTS PEOPLE FROM THE |
| | DRIVE THRU AREA TO WHERE. |
| | |
| | 3) EXIT SIGN MISSING FROM GARAGE STAIR |
| | ON FIRST FLOOR LIGHTING PLAN. |
| | |
| | 4) PLEASE EXPLAIN EXITING ARRANGEMENT |
| | FOR THE NORTHWEST OFFICE AND NORTHEAST |
| | OFFICE, THIRD FLOOR. |
| | |
| | 5) PLEASE EXPLAIN EXITING RATIONALE |
| | FROM THIRD FLOOR BRIDGE FROM COURTHOUSE |
| | COMMONS BUILDING TO THE EXISTING |
| | PARKING GARAGE. WHO PRESENTLY OWNS |
| | THE EXISTING PARKING GARAGE AND HOW |
| | DO YOU EXIT PEOPLE ONTO OTHER PERSONS |
| | PROPERTY. |
| | |
| | 6) EXIT SIGN APPEARS TO BE MISSING FROM |
| | CENTER STAIR 4TH FLOOR LIGHTING PLAN. |
| | |
| | 7) EMERGENCY LIGHTING MISSING AT EXIT |
| | DOORS ON FIFTH FLOOR LIGHTING PLAN (B). |
| | |
| | 8) EXIT SIGNS MISSING FROM ROOF LIGHTING |
| | PLAN. |
| | |
| | 9) FIRE ALARM NOTES # 17 AND 19 ARE |
| | INCORRECT. DUCT SMOKE DETECTORS WHEN |
| | ACTIVATED SHALL INITIATE AN ALARM NOT |
| | A SUPERVISORY SIGNAL. FIRE ALARM |
| | CIRCUITS SHALL BE CLASS A OR STYLE D |
| | OR BE FULLY ADDRESSABLE. FIRE ALARM |
| | SYSTEM SHALL BE UL LISTED FOR CENTRAL |
| | STATION SERVICE. |
| | |
| | 10) FIRE ALARM INITIATING DEVICES |
| | APPEAR TO BE MISSING FROM THE ROOF |
| | ELEVATOR MECHANICAL ROOM. |
| | |
| | 11) PLEASE PROVIDE UL NUMBERS FOR |
| | ALL FIRE RATED WALLS. |
| | |
| | 12) ALL RATED WALLS SHOULD HAVE DASHED |
| | LINES INDICATING ONE HOUR OR TWO |
| | HOUR ASSEMBLIES. |
| | |
| | 13) PLEASE VERIFY ALL EXIT DOORS |
| | SWINGS. |
| | |
| | 14) DOORS 6A1 AND 6A2 ON ROOF SWING |
| | IN THE WRONG DIRECTION. |
| | |
| | 15) ALL NEW RAMPS AND STAIRS SHALL |
| | HAVE HANDRAILS ON BOTH SIDES. |
| | |
| | 16) ELEVATOR WARNING SIGNS REQUIRED. |
| | |
| | 17) THE FIRE DEPARTMENT CONNECTION IS |
| | LOCATED ON THE WRONG SIDE OF THE |
| | BUILDING. |
| | |
| | MIKE CARSILLO, ASSISTANT FIRE MARSHAL |