| Date |
Text |
| 2007-03-22 11:12:31 | |
| | THIS REVIEW, #15 IS CONCERNING CORRIDOR REMOVAL./WRT. |
| 2007-03-22 09:55:52 | |
| | |
| | |
| | NONCOMPLIANT |
| | |
| | PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE |
| | COMPLIANCE AND RESUBMIT FOR REVIEW. |
| | |
| | 1} SHEETS E2.2A, E 2.3A, E2.4A AND E2.5A, THE FLOOR |
| | MUST HAVE EGRESS ILLUMINATION PER 7.8.AND 7.9, |
| | NFPA-101. PLACE FIXTURES ON PLAN TO SHOW COMPLIANCE. |
| | |
| | 2} SHEET E3.1A, CIRCUIT L1A-30 TO M1-1, IS LISTED AS A |
| | SPARE ON THE SCHEDULE. |
| | |
| | 3} CIRCUIT L1A-6 TO THE SECURITY ROOM RECEPTACLES ARE |
| | INCORRECTLY LISTED AS "MAIL ROOM" ON THE SCHEDULE. |
| | |
| | 4} NOTE #7 REFERENCES THE ELEVATOR MACHINE ROOM DETAIL |
| | WHICH HAS BEEN REMOVED FROM THIS SHEET. NOTE SHOULD BE |
| | CORRECTED TO REFLECT THE DETAIL ON THE CORRECT SHEET, |
| | E4.1. |
| | |
| | 5} CIRCUIT L1A-2 NOW LOCATED IN THE ELECTRIC ROOM, IS |
| | INCORRECTLY MARKED AS IN THE LOBBY ON THE SCHEDULE. |
| | |
| | 6}SHEET E3.3A, SHOW THE DOOR ON THE ELECTRICAL ROOM TO |
| | INDICATE THE EQUIPMENT IS PROPERLY GUARDED PER 110.27. |
| | |
| | 7} SHEET E4.1 REVISE THIRD FLOOR ELECTRICAL ROOM TO |
| | INCLUDE A DOOR, 110.27 NEC. |
| | |
| | 8} SHEET E5.1 DOES NOT INDICATE A FEED FOR PANEL "TB" |
| | SHOWN ON SHEET E3.1B. IT IS UNDERSTOOD THAT IT WILL BE |
| | SUPPLIED WITH THE BOOTH EQUIPMENT AS NOTED ON THE PANEL |
| | SCHEDULE BUT NO INDICATION OF FEEDER AND OCP ORIGIN. |
| | |
| | 9} SHEET E3.1A LISTS THE ELEVATOR MMACHINE ROOM AS A |
| | MECHANICAL ROOM, PLEASE CORRELATE. |
| | |
| | 10} REGARDING SHEET E4.1, THE ELEVATOR MACHINE ROOM IS |
| | NOT COMPLETE, THE DISCONNECTS FOR ELEVATORS 4 & 5 ARE |
| | NOT SHOWN. |
| | |
| | 11} E4.1, THE ELEVATOR MACHINE ROOM FOR ELEVATORS 1, 2, |
| | AND 3 DOES NOT INCLUDE THE DISCONNECTS FOR SAME. ALSO |
| | THOSE DISCONNECTS ARE NOT MARKED WITH CIRCUIT NUMBERS |
| | ON SHEET E3.1. PANEL EL1AIS INCORRECTLY LOCATED ON |
| | ONE OR THE OTHER SHEET. |
| | |
| | 13} THE ELECTRICAL ROOM LAYOUT ON E4.1 DOES NOT |
| | CORRELATE WITH SAME ON SHEET E3.1A. |
| | |
| | NOTE: SHEETS E2.1A, E2.6A, E3.1A, E3.2A, E3.3A, E3.4A, |
| | E3.5A AND E5.1, HAVING BEEN REVIEWED AS COMPLIANT AND |
| | HAVE BEEN STAMPED AND MADE PART OF THE FILED DOCUMENTS. |
| | TWO SETS HAVE BEEN STAMPED FOR RETURN TO TO THE |
| | CONTRACTOR. |
| | |
| | IF THERE ARE ANY QUESTIONS PLEASE CALL. |
| | |
| | BILL TROBAUGH |
| | ELECTRICAL PLAN REVIEW. |