| Plan Review Notes For Permit 04042022 |
| Permit Number |
04042022 |
|
| Review Stop |
M |
| Sequence Number |
12 |
|
| Notes |
| Date |
Text |
| 2007-03-06 15:54:00 | REVISIONS SUBMITTED FOR PAGES M2.1A, M2.2, M2.3, M2.4, | | | M2.5 | | | | | | PG M2.2 DENIED: THE FIRE DAMPER EXCEPTION AS NOTED ON | | | PLAN DOES NOT APPLY TO THIS PROJECT AS IT WAS PERMITTED | | | UNDER FBC 2001. THE CODE SECTION CITED DOES NOT RELATE | | | TO FBC,M 2001. PLEASE CORRECT AND RESUBMIT. | | | | | | PG M2.5 CITES THE SAME CODE SECTION. HOWEVER, THE FIRE | | | DAMPERS IN QUESTION ARE INSTALLED AND SHOWN ON PLAN. | | | SINCE THE EXCEPTION IS NOT BEING CLAIMED, THIS PAGE HAS | | | PASSED REVIEW. | | | | | | ALL OTHER MECHANICAL PLAN REVIEW COMMENTS AND PROVISOS | | | HAVE BEEN SATISFIED TO THIS POINT. | | | | | | RONALD J REGUEIRO | | | 561-805-6734 | | | [email protected] |
|