| 2004-05-04 00:00:00 | 1) SITE PLAN DOES NOT ILLUSTRATE NEW |
| | OR EXISTING FIRE HYDRANTS. |
| | |
| | 2) DEMOLITION, RENOVATION, AND |
| | CONSTRUCTION TO COMPLY WITH |
| | NFPA 241. |
| | |
| | 3) TEMPORARY STANDPIPE SYSTEMS |
| | REQUIRED WHEN THE BUILDING REACHES |
| | THREE FLOORS OR THIRTY FEET IN HEIGHT. |
| | |
| | 4) STAIRS ARE TO BE KEPT UP WITH |
| | CONSTRUCTION. |
| | |
| | 5) TACTILE SIGNAGE REQUIRED AT EXITS. |
| | |
| | 6) ALL SHAFTS THAT ARE LARGE ENOUGH |
| | FOR PERSONS TO FALL INTO MUST BE |
| | MARKED "SHAFTWAY" WITH 6" LETTERS. |
| | |
| | 7) BUILDING ADDRESSES REQUIRED. A |
| | MINIMUM OF AT LEAST 6" HIGH NUMBERS. |
| | |
| | 8) KNOX-BOXES WILL BE REQUIRED. |
| | |
| | 9) LOCKING KNOX-BOX CAPS WILL BE |
| | REQUIRED FOR THE FIRE DEPARTMENT |
| | CONNECTIONS. |
| | |
| | 10) ALL NEW STAIRS AND RAMPS ARE |
| | REQUIRED TO HAVE HANDRAILS ON BOTH |
| | SIDES. |
| | |
| | 11) BUILDINGS WILL BE LOCATED IN THE |
| | CITY FIRE LIMITS. CETRAIN RESTRICTIONS |
| | WILL APPLY. PLEASE SEE APPENDIX F, |
| | LOCAL AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE. |
| | |
| | 12) IT APPEARS THAT STAIR A-B-1 |
| | TERMINATES INTO THE LOADING DOCK. |
| | PLEASE EXPLAIN RATIONALE. |
| | |
| | 13) HOW IS ACCESS PROVIDED INTO THE |
| | FIRE PUMP ROOM WHEN THE SECURITY |
| | GRILL IS DOWN FOR THE GARAGE AREA. |
| | |
| | 14) PLEASE INDICATE WHICH ELEVATOR(S) |
| | WILL BE STRETCHER ACCESSIBLE. |
| | |
| | 15) PLEASE PROVIDE A LIFE SAFETY PLAN |
| | INDICATING OCCUPANT LOADS, TRAVEL |
| | DISTANCES, DEAD-ENDS, ETC. |
| | |
| | 16) PLEASE DISPLAY ALL TENANT SEPARATION |
| | WALLS. |
| | |
| | 17) PLEASE VERIFY DOOR SWINGS. DOOR 111 |
| | APPEARS TO SWING IN THE WRONG DIRECTION. |
| | |
| | 18) HOW IS EXIT ACCESS ACHIEVED TO |
| | DOOR 202. A COLUMN AND A PARKING |
| | SPACE IS PRESENT. PLEASE EXPLAIN. |
| | |
| | 19) SAME CONDITION APPEARS TO EXIST |
| | FOR DOOR 301. SAME FOR DOOR 401. |
| | |
| | 20) PLEASE PROVIDE PRESCRIPTIVE |
| | STRENGTH REQUIREMENTS FOR ALL HANDRAILS |
| | AND GUARDRAILS. |
| | |
| | 21) TWO DOORS CLOSELY SPACED AT STAIR |
| | A-1, LEVEL 3. HOW DO PEOPLE MOVE |
| | QUICKLY IS TWO DIRECTIONS IN THIS SMALL |
| | AREA. |
| | |
| | 22) STAIR IDENTIFICATION SIGNS REQUIRED. |
| | THESE SIGNS SHALL IDENTIFY STAIR |
| | NUMBER, TERMINUS TOP AND BOTTOM, AND |
| | FLOOR NUMBER. |
| | |
| | 23) PLEASE INDICATE INTERIOR FINISH |
| | FOR WALL AND CEILINGS. |
| | |
| | 24) DOES THE CORRIDOR CONNECT TO THE |
| | EXISTING UNSPRINKLERED PARKING GARAGE. |
| | PLEASE ADVISE. PLEASE SEE FS 553.895 (2) |
| | |
| | 25) PLEASE IDENTIFY HEIGHT OF |
| | CONNECTION BRIDGE. A MINIMUM OF 13 FEET |
| | 6 INCHES WILL BE REQUIRED. |
| | |
| | 26) DOOR SCHEDULES DO NOT IDENTIFY |
| | REQUIRED FIRE RATINGS. |
| | |
| | 27) PLEASE EXPLAIN IF CAFE WILL BE |
| | COOKING ANY ITEMS THAT PRODUCE SMOKE |
| | OR GREASE LADEN VAPORS. IF SO WHERE |
| | WILL THE REQUIRED GREASE HOOD DUCT |
| | TERMINATE. |
| | |
| | 28) LOADING DOCK WILL BE REQUIRED TO |
| | BE FIRE SPRINKLER PROTECTED. |
| | |
| | 29) A TWO HOUR FIRE SEPARATION WILL |
| | BE REQUIRED FOR ANY PARKING AREAS AND |
| | ADJACENT AREAS. |
| | |
| | 30) PLEASE DISPLAY ALL FIRE RATED WALLS |
| | AND SHAFTS AND THEIR APPROPRIATE |
| | HOURLY RATINGS. PLEASE PROVIDE UL |
| | NUMBERS. |
| | |
| | 31) NO EXIT SIGNS AND EMERGENCY LIGHTS |
| | SHOWN ON FIRST FLOOR A, PAGE E2.1A. |
| | |
| | 32) WHERE IS THE SECOND EXIT IDENTIFIED |
| | ON FIRST FLOOR B, PAGE E2.1B. ALSO |
| | EXIT SIGNS SHOWN IN WITHIN PARKING |
| | SPACES. |
| | |
| | 33) WHERE DOES THE EXIT SIGN FROM THE |
| | CORRIDOR TO THE BRIDGE LEAD TO. |
| | |
| | 34) EXIT SIGN MISSING INFRONT OF EXIT |
| | FOURTH FLOOR SECTION A, PAGE E2.4A |
| | SAME CONDITION EXISTS ON PAGE E2.5A. |
| | |
| | 35) EMERGENCY LIGHTING REQUIRED IN |
| | FIRE PUMP ROOM. |
| | |
| | 36) PLEASE INDICATE OCCUPANT LOADS |
| | FOR ALL STAIRS. AT LEAST ONE STAIR |
| | IS BEING SHARED WITH THE GARAGE. |
| | |
| | 37) NO FIRE SPRINKLER DRAWINGS |
| | PROVIDED WITH PLANS. |
| | |
| | 38) NEW FIRE ALARM SYSTEM SHALL BE |
| | UL LISTED FOR CENTRAL STATION SERVICE. |
| | |
| | 39) PLEASE PROVIDE CONSTRUCTION TYPE |
| | FOR THE BUILDING. |
| | |
| | 40) PLEASE DISPLAY STANDPIPE SYSTEM |
| | LOCATIONS. |
| | |
| | 41) MORE DETAILS REQUIRED FOR FIRE |
| | PUMP. |
| | |
| | MIKE CARSILLO, ASSISTANT FIRE MARSHAL |
| | 835-2910 |