| 2004-05-28 00:00:00 | BUILDING PLAN REVIEW |
| | PERMIT: 04042022 |
| | ADD: 477 3RD ST. |
| | CONT: PLAN REVIEW |
| | CONTACT WEST RAILROAD LIMITED |
| | PROJECT SUPERVISOR: PATTI LUDLOW |
| | TEL: (561)368-2544 EXT.22 |
| | FL BLD CODE= 2001 FLORIDA BUILDING CODE |
| | |
| | 1ST PLAN REVIEW |
| | ACTION: DENIED |
| | |
| | 1) PROVIDE NOC RECORDED WITH THE CLERK |
| | OF COURT BEFORE A PERMIT CAN BE ISSUED. |
| | |
| | 2) PROVIDE 2 CURRENT COPIES OF SIGNED & |
| | SEALED SURVEYS WITH PROPOSED IMPROVEMENT |
| | TO BE COMPLETED. |
| | |
| | 3)FL S. S. 553.71(7) " THRESHOLD |
| | BUILDING" MEANING ANY BUILDING WHICH IS |
| | GREATER THAN (3) STORIES OR 50 FT IN |
| | HEIGHT, OR WHICH HAS AN ASSEMBLY OCCUPAN |
| | CY CLASSIFICATION AS DEINED IN THE |
| | FLORIDA BUILDING CODE WHICH EXCEEDS |
| | 5,000 SQ FT IN AREA AND AN OCCUPANT |
| | CONTENT OF GREATER THAN 500 PERSONS. |
| | 105.13.1 THE ENFORCING AGENCY SHALL |
| | REQUIRE A SPECIAL INSPECTOR TO PERFORM |
| | SRUCTURAL INSPECTIONS ON A THRESHOLD |
| | BUILDING PURSUANT TO A STRUCTURAL INSPEC |
| | TION PLAN PREPARED BY THE ENGINEER OF |
| | RECORD. THE STRUCTURAL INSPECTION PLAN |
| | MUST BE SUBMITTED TO THE ENFORCING AGEN- |
| | CY PRIOR TO THE ISSUANCE OF A BUILDING |
| | PERMIT FOR THE CONSTRUCTION OF A THRESH- |
| | OLD BUILDING. THE PURPOSE OF THE SRUCTUR |
| | AL INSPECTION PLAN IS TO PROVIDE SPECIF- |
| | IC INSPECTION PROCEDURES AND SCHEDULES |
| | SO THAT THE BUILDING CAN BE ADEQUATELY |
| | INSPECTED FOR COMPLIANCE WITH THE |
| | PERMITTED DOCUMENTS. |
| | A THRESHOLD INSPECTOR SHALL ALSO BE |
| | REQUIRED TO BE SIGNED ON SEE HAROLD |
| | PISKURA (561)805-6711. |
| | (3) SETS OF ALL DOCUMENTS ARE |
| | REQUIRED FOR THRESHOLD BUILDINGS. |
| | |
| | 4) FL BLD CODE 1804.2.2 QUESTIONABLE |
| | SOILS, WHERE THE BEARING CAPACITY IS |
| | NOT DEFINETLY KNOWN OR IS IN QUESTION. |
| | WHERE THE BEARING CAPACITY OF THE SOIL I |
| | S NOT DEFINITEY KNOWN, OR IS IN QUESTION |
| | THE BUILDING OFFICIAL MAY REQUIRE EXPLOR |
| | ATIONS, TEST OR OTHER ADEQUATE PROOF AS |
| | TO THE PERMISSIBLE SAFE BEARING |
| | CAPACITY. REQUIRED TEST AND RECOMMENDA- |
| | TIONS SUBMITTED TO VERIFY BEARING CAPA- |
| | CITY SHALL BE CERTIFIED BY A GEOTECH- |
| | NICALREPORT FROM A DESIGN PROFESSIONAL P |
| | ROPERLY LICENSED IN THE STATE OF |
| | FLORIDA. |
| | |
| | 5) PLANS, SPECIFICATIONS,REPORTS OR |
| | OTHER DOCUMENTS PREPARED BY THE DESIGN |
| | PROFESSIONAL AND BEING FILED FOR PUBLIC |
| | RECORD SHALL HAVE THE SIGNATURE AND |
| | SEAL OF THE DESIGN PROFESSIONAL AFFIXED |
| | TO THE DOCUMENT. |
| | FL STATE STAT: 61G15-23.002 ENGINEERS |
| | FL ATATE STAT: 61G16.003 ARCHITECTS |
| | |
| | 6) FIRE SPRINKLERS 903.8.1 BUILDINGS |
| | 3 STORIES OR MORE IN HEIGHT SHALL |
| | REQUIRE FIRE SPRINKLER PLANS BEFORE THE |
| | ISSUANCE OF A BUILDING PERMIT.THEY ARE |
| | TO BE PART OF THE BUILDING SET OF PLANS. |
| | SEPERATE PLANS WILL BE REQUIRED FOR THE |
| | FIRE APRINKLER PERMIT. |
| | |
| | 7) PLANS DO NOT INDICATE WHAT BUILDING |
| | TYPE? FOR THIS REVIEW IT WILL BE CONSID- |
| | ERED A TYPE II BUILDING. BUILDING IS |
| | 70' TALL. |
| | |
| | 8) PLANS ARE NOT CLEAR AS TO WHERE THE |
| | PROPERTY LINE IS? PROVIDE A DIMENSION |
| | FROM THE BUILDING TO THE PROPERTY LINE. |
| | THERE MAY BE TABLE 600 ISSUES (OPENINGS) |
| | ON THE EAST AND NORTH SIDES OF THE BUILD |
| | ING. 0'-3' NO OPENINGS, 3'-10',10% ALLOW |
| | ABLE OPENINGS. ALSO NOT 705.1.1.2 OPEN- |
| | INGS WITHIN 15'-0" REQUIRE OPENING |
| | PROTECTIVES, DEPENDING ON WHERE THE |
| | PROPERTY LINE IS LOCATED THE DETERMINA- |
| | TION IF THE PARKING GARAGE CAN REMAIN A |
| | OPEN STRUCTURE OR IF IT WILL NEED TO BE |
| | A ENCLOSED PARKING STRUCTURE. |
| | |
| | 9) PLANS ARE NOT THROUGH ENOUGH FOR THE |
| | SKY BRIDGE, IS THIS TO BE PART OF THIS |
| | PERMIT? HOW WILL IT TIE IN ON THE OTHER |
| | SIDE OF THE STREET? WHAT TYPE OF AGREE- |
| | MENTS HAVE BEEN MADE WITH THE COUNTY FOR |
| | THE SKY BRIDGE? |
| | |
| | 10) SHEET A.31.01 IS THIS A MISPRINT, |
| | BANK FINISH FLOOR FOR THE 1ST FLOOR TO |
| | BE AT 20'-0" ELEVATION? THE ELEVATIONS |
| | ON THE EXTERIOR ARE BETWEEN 8.53/9.92'? |
| | |
| | 11) RESTROOM 125 DOESN'T HAVE 12" ON THE |
| | PUSH SIDE OF LATCH, SEE: |
| | 11-4.13.6 MANEUVERING CLEARENCES |
| | AT DOORS. MINIMUM MANEUVERING CLEARENCES |
| | AT DOORS THAT ARE NOT AUTOMATIC OR |
| | POWER-ASSISTED SHALL BE AS SHOWN IN |
| | FIG. 25. THE FLOOR OR GROUND AREA WITH |
| | IN THE REQUIRED CLEARENCES SHALL BE |
| | CLEAR & LEVEL. |
| | |
| | 12) CAFE TOLIET, 1202.4.1 TOLIET ROOMS |
| | SHALL NOT OPEN DIRECTLY INTO A ROOM USED |
| | FOR THE PREPERATION OF FOOD FOR SERVICE |
| | TO THE PUBLIC. |
| | |
| | 13) WINDOW 120 RATED GLASS, TABLE 704.1 |
| | 1 HR WALL. |
| | |
| | 14) 3003.4.1 ELEVATOR STRETCHER REQUIRE- |
| | MENTS SEE ELE 1 & 2. |
| | |
| | 15) SHEET A.31.07,A31.09, A.31.11 AND |
| | A31.13 ALL INDICATE A COLUMN THROUGH THE |
| | 5'-0" HANDICAPPED ACCESS ISLE. |
| | |
| | 16) SHEET A.31.07 HANDICAPPED PARKING @ |
| | DOOR# 113 (SPACE# 67) DOESN'T HAVE A |
| | ACCESS ISLE IN FRONT OF THE VEHICLE, |
| | CAUSING THE PERSON TO WHEEL BEHIND THE |
| | VEHICLE, IN THE INCOMING TRAFFIC LANE. |
| | |
| | 17) TICKET BOOTH IS THIS A FABRICATED |
| | BUILDING? NO DETAILS FOR CONSTRUCTION? |
| | |
| | 18) 2ND- 5TH FLOOR, THE INTERIOR HALL |
| | COLUMNS ARE WITHIN 6" OF THE ENTRY DOORS |
| | TO EACH UNIT. SEE 11-4.13.6 CLEARENCE |
| | @ DOORS, 12" REQUIRED ON THE PUSH SIDE. |
| | |
| | 19) A.31.02 OFFICE SPACE SOUTHEAST & |
| | SOUTHWEST WILL REQUIRE 2 EXITS,1020.1(4) |
| | |
| | 20) PROVIDE INFORMATION ON THE CANOPY |
| | OVER THE ENTRY WAY? |
| | |
| | 21) FL. BLD CODE 1606.1.7 THE FOLLOWING |
| | INFORMATION RELATED TO WIND SHALL BE |
| | SHOWN ON THE CONSTRUCTION DRAWINGS, |
| | 1)- BASIC WIND SPEED, MPH |
| | 2)- WIND IMPORTANCE FACTOR, & BUILDING |
| | CATEGORY |
| | 3)- WIND EXPOSURE |
| | 4)- INTERNAL PRESSURE COEFFICIENT, |
| | 5)- COMPONENTS & CLADDING, THE DESIGN |
| | WIND PRESSURES IN TERMS OF PSF. |
| | |
| | 22)FL BLD CODE 1606.1.5: COMPONENTS & |
| | CLADDING, PROVIDE 2 COPIES(3 IF THRESH- |
| | OLD OR RESIDENT INSPECTOR) OF PRODUCT |
| | TESTING REPORTS,MISSING REPORTS ARE AS |
| | FOLLOWS: |
| | A) WINDOWS |
| | B) EXTERIOR DOORS |
| | C) LOUVERS |
| | D) SKYLIGHTS |
| | E) TRUSS ANCHORS |
| | F) ROOFING ASSEMBLIES |
| | PRODUCT APPROVALS SUBMITTED WITH |
| | PERMIT APPLICATION AFTER OCTOBER 1, 2003 |
| | ARE REQUIRED TO COMPLY WITH THE FLORIDA |
| | PRODUCT APPROVAL SYSTEM. FOR INFORMATION |
| | PLEASE SEE THE STATE WEBSITE AT |
| | WWW.FLORIDABUILDING.ORG. PRODUCTS WITH |
| | STATEWIDE APPROVAL ARE REQUIRED TO BE |
| | SUBMITTED WITH A COVER SHEET THAT LISTS |
| | THE PRODUCT IDENTITY NUMBER FROM THE |
| | STATE. IF THE PRODUCT DOES NOT HAVE |
| | STATEWIDE APPROVAL, SUBMIT AN APPLICA- |
| | TION FOR LOCAL PRODUCT APPROVAL OR SITE |
| | SPECIFIC FORM PER RULE 9B-72. SEE |
| | ATTACHMENT. WWW.FLORIDABUILDING.ORG |
| | |
| | 23) STRUCTURAL PLANS MISSING THE FOUNDA- |
| | TION SCHEDULE, COLUMNS AND BEAMS. |
| | |
| | 24) PROVIDE ADDTIONAL INFO FOR THE FIRE |
| | RATING OF ALL STRUCTURAL ELEMENTS FOR |
| | TYPE II BUILDING. |
| | |
| | 25) FOUNDATION PLAN HAS THE 2ND FLOOR |
| | REINFORCING LEGEND ON IT? S1.1. |
| | |
| | 26) S2.1 COLUMN# 35 IS MISSING ON THIS |
| | SHEET? |
| | |
| | 27) S.3.1 THE 3RD FLOOR FRAMING PLAN |
| | INDICATES A HALLWAY CONNECTION, A CORRI- |
| | DOR ON THE EAST SIDE OF THE BUILDING, |
| | PLANS ARE NOT CLEAR AS TO A SECONDARY |
| | COLUMN LINE, DETAILS ARE MISSING. ALSO |
| | BETWEEN COLUMN 56 & 39 SHOULD THERE BE |
| | A COLUMN BETWEEN? |
| | |
| | 28) SHOULD THERE ALSO BE A COLUMN LINE |
| | NEXT TO THE PARKING GARAGE STRUCTURE? |
| | |
| | BEFORE A PERMIT TO CONSTRUCT, MAY |
| | BE ISSUED, IMPACT FEES MUST BE PAID TO |
| | PALM BEACH COUNTY. THE ACTUAL PERMIT |
| | SET OF PLANS MUST BE STAMPED BY THAT |
| | OFFICE, AND A COPY OF THE PAID RECEIPT |
| | ATTACHED TO THE PERMIT APPLICATION. |
| | PLEASE CALL (561)233-5025 FOR MORE |
| | INFORMATION. |
| | |
| | LOOK FOR COMMENTS BY THE OTHER PLAN |
| | REVIEW DISCIPLINES THAT MAY BE WRITTEN |
| | ON THE APPLICATION, PLANS, OR ATTACHED |
| | SEPARATELY. WHEN RESUBMITTING PLANS |
| | PLEASE CLEARLY INDICATE THE REVISION AND |
| | REMOVE AND REPLACE ANY PAGES AS NECESS- |
| | ARY. SUBMIT (1) SET OF OLD DRAWINGS WITH |
| | THE PLANS WHEN RESUBMITTING PLANS. A |
| | TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | COMMENTS WILL GREATLY ACCELARATE YOUR |
| | PERMIT. |
| | JIM WITMER |
| | BUILDING PLAN REVIEW |
| | (561)805-6715 |
| | |
| | |
| | |
| | TEL: (561)805-6715 |
| | FAX: (561)659-8026 |