2004-06-09 00:00:00************** UNSAT *****************
  
 PLEASE SEE SOME NOTES FROM FIRST REVIEW
 NOT ADDRESSED.
  
 1)NOTE: PLEASE SEE FS 471.219 AND FAC
 61G1-16.004 WHICH REQUIRES ALL LICENSE
 #'S TO BE PRINTED ON TITLE BLOCK.
 PREVIOUS PLANS WERE SENT OFF TO STATE
 DBPR FOR THIS AND PLANS STILL DO NOT
 INCLUDE #'S.??
  
 2)NOTE: PLEASE CLARIFY SHOW WINDOW
 RECEPTS. PLANS NOW SHOW REQUIRED RECEPTS
 TO BE REMOVED? PLEASE SEE 210.62. THESE
 ARE REQUIRED.
  
 3)NOTE: PLEASE ALSO SEE 600.5. PANEL
 SCHEDULE SHOWS REQUIRED SIGN CIRCUIT TO
 BE REMOVED? THIS IS REQUIRED.
  
 PLEASE SEE NOTE #1, THIS IS REQ'D FOR
 ALL SHEETS AND PLANS. PLEASE SEE ONE SET
 OF PLANS ARE BEING RETAINED FOR FILE.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  