| 2004-05-04 00:00:00 | ************* UNSAT ************ |
| | |
| | 1)NOTE: PLEASE CLARIFY IF NEW OR EXIST- |
| | -ING SIGN CIRCUIT? 600.5 |
| | |
| | 2)NOTE: PLEASE SEE 700.12E FOR CIRCUIT- |
| | -ING OF EM/EXT LTS. |
| | TO BE ON SAME BRANCH CIRCUIT SUPPLYING |
| | GEN LT IN AREA. |
| | |
| | 3)NOTE: PLEASE SHOW ALL CIRCUITING ON |
| | PLANS AND CORRELATE WITH THE SUBMITTED |
| | PANEL SCHEDULE. |
| | |
| | 4) NOTE: PLEASE SHOW ALL CONTINUOUS LOAD |
| | -S AT 125%(LIGHTING ETC)(LARGEST MOTORS) |
| | 215.2,215.3,230.42,210.19A,210.20A ETC |
| | PLEASE SHOW LOAD CALCULATIONS, |
| | PLEASE SHOW PER2002 NEC COMMERCIAL BLD |
| | 220.3,220.10,220.11,220.13 ETC. |
| | RESIDENTIAL LOAD CALC SHOWN. |
| | PLEASE ALSO SEE LOAD CALCS INDICATE |
| | 26 FIXTURES @180 VA?? PLEASE VERIFY?? |
| | |
| | 5)NOTE: PLEASE SEE PANEL SCHEDULE, |
| | SHOWS PANEL AS BEING MLO AND MCB??? |
| | PLEASE CLARIFY. |
| | |
| | 6)NOTE: PLEASE SEE FAC 61G1-16.004, |
| | PLEASE PROVIDE ALL LICENSE #'S ON TITLE |
| | BLOCK. PLEASE ALSO SEE FS 481.219 FOR |
| | REQ'D CA #. ALSO REQ'D ON TITLE BLOCK. |
| | PLEASE SEE FS 481.221 WHICH REQ'S A |
| | SIGNATURE, DATE AND SEAL. |
| | PLEASE PROVIDE A COPY OF |
| | LICENSE/ TO VERIFY LEGAL SIGNATURE FOR |
| | FILE. DBPR/ FBPE'S, INITIALS ARE NOT |
| | PERMITTED. |
| | |
| | 7)NOTE: PLANS SHOW "J" BOXES FOR REQ'D |
| | EGRESS LIGHTING. PLEASE VERIFY SOME SORT |
| | OF FIXTURE FOR MIN EGRESS LIGHTING WILL |
| | BE REQ'D. LS101 5-8 |
| | |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |