2004-06-25 00:00:00PROVISO:
 1.RETURN AIR JUMPER FROM THE MASTER
 BEDROOM IS NOT SIZED.GRILLES INDICATED
 ARE 14" X 14".RETURN AIR JUMPER SHALL
 BE A MINIMUM OF 16" PER THE REVISED
 2001 FBC(M) 601.4 EXCEPTION #1 & 3.
  
 2.RETURN AIR JUMPER FROM BEDROOM 1
 (EXISTING) SHALL BE A MINIMUM OF 9".
  
 3.PER 2001 FBC(M) 304.7, CONDENSER
 UNIT SLAB SHALL BE A MINIMUM OF 3 1/2"
 EXTENDING A MINIMUM OF 2 1/2" ABOVE
 ADJOINING FINISHED GRADE.
  
 4.AUXILIARY DRAIN PAN WITH OVERFLOW
 PROTECTION REQUIRED, 2001 FBC(M) 307.2.3
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.