| Plan Review Notes For Permit 04041978 |
| Permit Number |
04041978 |
|
| Review Stop |
M |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2004-06-25 00:00:00 | PROVISO: | | | 1.RETURN AIR JUMPER FROM THE MASTER | | | BEDROOM IS NOT SIZED.GRILLES INDICATED | | | ARE 14" X 14".RETURN AIR JUMPER SHALL | | | BE A MINIMUM OF 16" PER THE REVISED | | | 2001 FBC(M) 601.4 EXCEPTION #1 & 3. | | | | | | 2.RETURN AIR JUMPER FROM BEDROOM 1 | | | (EXISTING) SHALL BE A MINIMUM OF 9". | | | | | | 3.PER 2001 FBC(M) 304.7, CONDENSER | | | UNIT SLAB SHALL BE A MINIMUM OF 3 1/2" | | | EXTENDING A MINIMUM OF 2 1/2" ABOVE | | | ADJOINING FINISHED GRADE. | | | | | | 4.AUXILIARY DRAIN PAN WITH OVERFLOW | | | PROTECTION REQUIRED, 2001 FBC(M) 307.2.3 | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561) 805-6719. |
|