| Notes |
| Date |
Text |
| 2004-06-16 00:00:00 | ********* UNSAT ************** | | | | | | COMPLETED ELECTRICAL PLANS ARE NOW BEING | | | SUBMITTED FOR REVIEW. | | | | | | 1)NOTE: PLEASE SEE MISSING RECEPTS PER | | | 210.52. 2',6',12 RULE. PLEASE SEE ONE | | | SET HAS AREAS HIGH-LIGHTED. | | | | | | 2)NOTE: PLEASE SEE MISSING RECEPTS PER | | | 210.52E FRONT/REAR. WP/GFI | | | | | | 3)NOTE: PLEASE SEE MISSING RECEPTS THAT | | | ARE REQUIRED TO BE WITH/IN 3' OF SINKS/ | | | LAV'S. 210.52D/210.11C3 | | | | | | 4)NOTE: PLEASE SEE SD IS REQUIRED TO | | | INSIDE BEDROOM #4. DOORWAY APPEARS TO | | | HAVE A HEADER. PLEASE ALSO SEE SD OUT- | | | -SIDE MASTER BEDRM. NFPA-72 | | | | | | 5 )NOTE: PLEASE SEE MISSING REQ'D EGRESS | | | LIGHTING AND/OR CLARIFY EGRESS LIGHTING | | | PER 210.70 AND LS-101 5-8 | | | DIN RM/ LIB RM. | | | | | | PLEASE SEE PERMIT APPLICATION WAS NOT | | | IN PACKAGE. THIS WILL BE REQUIRED. | | | | | | PLEASE REMOVE ALL OLD/VOIDED SHEETS AND | | | INSERT NEW SHEETS INTO TWO COMPLETE SETS | | | FOR REVIEW AND STAMPING. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE TO CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CITY OF WEST PALM BEACH | | | CONSTUCTION SERVICES DEPT. | | | 561-805-6717 | | | [email protected] |
|