Plan Review Notes
Plan Review Notes For Permit 04041962
Permit Number 04041962
Review Stop E
Sequence Number 2
Notes
Date Text
2004-08-03 00:00:00*********** PROVISO/REVISION **********
  
 PLEASE SEE NOTES FROM FIRST REVIEW.
  
 1)NOTE: PLEASE SEE PLANS STILL INDICATE
 EQUIPMENT GROUNDING CONDUCTORS INSTALLED
 FROM METER TO THE FIRST MEANS OF DISC.
 PLEASE SEE 250.6,250.24, THIS IS NOT
 PERMITTED.
 EQUIPMENT GROUNDING CONDUCTORS ARE ONLY
 INSTALLED AFTER THE FIRST MEANS OF
 DISCONNECT.
  
 2)NOTE: PLEASE CORRELATE LOAD CALCULAT-
 -IONS WITH LOAD INDICATED ON MECH PLANS
 FOR "HEAT" KW.
  
  
 PLEASE SUBMIT THE ABOVE FOR REVIEW ALONG
 WITH ANY OTHER REVISIONS BEFORE ROUGH
 ELECTRICAL INSPECTION IS CALLED IN.
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
 IF PLANS COME BACK FOR ANY CORRECTIONS
 FROM OTHER PLANS REVIEWS, PLEASE MAKE
 CORRECTIONS AT THIS TIME BEFORE PERMIT
 IS ISSUED.