| Plan Review Notes For Permit 04041962 |
| Permit Number |
04041962 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2004-08-03 00:00:00 | *********** PROVISO/REVISION ********** | | | | | | PLEASE SEE NOTES FROM FIRST REVIEW. | | | | | | 1)NOTE: PLEASE SEE PLANS STILL INDICATE | | | EQUIPMENT GROUNDING CONDUCTORS INSTALLED | | | FROM METER TO THE FIRST MEANS OF DISC. | | | PLEASE SEE 250.6,250.24, THIS IS NOT | | | PERMITTED. | | | EQUIPMENT GROUNDING CONDUCTORS ARE ONLY | | | INSTALLED AFTER THE FIRST MEANS OF | | | DISCONNECT. | | | | | | 2)NOTE: PLEASE CORRELATE LOAD CALCULAT- | | | -IONS WITH LOAD INDICATED ON MECH PLANS | | | FOR "HEAT" KW. | | | | | | | | | PLEASE SUBMIT THE ABOVE FOR REVIEW ALONG | | | WITH ANY OTHER REVISIONS BEFORE ROUGH | | | ELECTRICAL INSPECTION IS CALLED IN. | | | IF THERE ARE ANY QUESTIONS, PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CITY OF WEST PALM BEACH | | | CONSTUCTION SERVICES DEPT. | | | 561-805-6717 | | | [email protected] | | | IF PLANS COME BACK FOR ANY CORRECTIONS | | | FROM OTHER PLANS REVIEWS, PLEASE MAKE | | | CORRECTIONS AT THIS TIME BEFORE PERMIT | | | IS ISSUED. |
|