2004-05-14 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
 FBC-2001 CHAPTER 11
 WPB CITY CODE
  
 1) SHT A10 BREAK ROOM SINK, SHOW KNEE
 CLEARANCE 11-4.24.3, SINK DEPTH 11-4.24.
 4, CLEAR FLOOR SPACE 11-4.24.5, AND EX-
 POSED PIPES AND SURFACES 11-4.24.6
 2) SHT A10 TOILET ROOM ELEVATIONS, SHOW
 WATER CLOSET HEIGHT 11-4.16.3, FLUSH
 CONTROLS 11-4.16.5, AND LAV HEIGHT 11-4.
 19.2.
 3) SHT A10 SUBMIT DETAIL FOR DRINKING
 FOUNTAIN PER SECTION 11-4.15 AND ALL
 SUBSECTIONS.
 4) SUBMIT A WATER RISER ISOMETRIC SHOW-
 ING ALL WATER HAMMER ARRESTORS REQUIRED
 BY SECTION 604.9 LOCATED NEAR THE FIX-
 TURE IN AN "EFFECTIVE RANGE" NOT IN THE
 CEILING. PDI-WH 201 AND MANUF. INSTALL.
 INSTRUCTIONS. SECTION 104.3.1.1
 5) SHT M1 INDICATES THAT CONDENSATE FROM
 AIR HANDLER UNITSTO DRAIN INTO THE FLOOR
 DRAIN. THIS IS NOT ALLOWED PER CITY WPB
 CODE SECTION 90-203. CONDENSATE SHALL
 DRAIN SEPARATELY OUTSIDE THE BLDG. TO
 A DRYWELL, CATCH BASIN, OR A STORM DRAIN
  
 REVIEW BY KEN STEVENS