2004-05-07 00:00:00DENIED:
 1.PLEASE PROVIDE OUTSIDE AIR
 CALUCALTIONS PER 2001 FBC(M) 403.3.
  
 2.FAN SHUT DOWN BY DUCT SMOKE
 DETECTORS REQUIRED FOR SYSTEMS THAT THE
 AGGREGATE AIR IS GREATER THAN 2,000
 CFM. 2001 FBC(M) 606.2.2.
  
 3.FAN SHUT DOWN SHALL HAVE
 NOTIFICATION TO ALARM STROBE IN
 NORMALLY OCCUPPIED AREAS PER NFPA 90A
 4-4.4.3.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.