| Plan Review Notes For Permit 04041962 |
| Permit Number |
04041962 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2004-05-07 00:00:00 | DENIED: | | | 1.PLEASE PROVIDE OUTSIDE AIR | | | CALUCALTIONS PER 2001 FBC(M) 403.3. | | | | | | 2.FAN SHUT DOWN BY DUCT SMOKE | | | DETECTORS REQUIRED FOR SYSTEMS THAT THE | | | AGGREGATE AIR IS GREATER THAN 2,000 | | | CFM. 2001 FBC(M) 606.2.2. | | | | | | 3.FAN SHUT DOWN SHALL HAVE | | | NOTIFICATION TO ALARM STROBE IN | | | NORMALLY OCCUPPIED AREAS PER NFPA 90A | | | 4-4.4.3. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561) 805-6719. |
|