Plan Review Notes
Plan Review Notes For Permit 04041962
Permit Number 04041962
Review Stop E
Sequence Number 1
Notes
Date Text
2004-05-08 00:00:00*************** UNSAT *****************
  
 1)NOTE: PLEASE SEE FAC 61G15-23.002.
 PLEASE SEE THAT PRINTED NAME AND LICENSE
 # OF ENGINEER IS ALSO REQ'D IN TITLE
 BLOCK FOR THE PERSON SIGNING AND SEALING
 PLANS. THIS IS REQ'D FOR ALL SHEETS AND
 TRADES WEATHER OR NOT COMMET IS MADE BY
 OTHER REVIEWERS.
  
 2)NOTE: PLEASE SEE 700.12E . EM LTS./
 NIGHT LT FIXTURES?THESE ARE TO BE
 WIRED AHEAD OF LOCAL LIGHTING BRANCH
 CIRCUITS.
  
 3)NOTE: PLEASE PROVIDE WIND LOAD FOR
 LT/LT POLE FOR PARKING LOT LTS.
 FBC 140 MPH.
  
 4)NOTE: PLEASE SEE 250.6,250.24.\
 NO EQUIPMENT GROUNDING CONDUCTORS ARE
 INSTALLED BETWEEN METER AND FIRST MEANS
 OF DISCONNECT.
  
 5 )NOTE: PLEASE SHOW LOAD CALCULATIONS,
 PLEASE SHOW PER
 220.3,220.10,220.11,220.13 ETC.
 PLEASE ALSO SHOW ALL CONTINOUS LOADS
 AT 125% PER 215.3,230.42
 PLEASE SEE LOAD IS NOW SHOWN AT CONNECT-
 -ED?415.52A'S . PLEASE SEE SEC'S ARE
 500 MCM WHICH IS RATED FOR 380A'S 310.16
 75> DEGREE COL.
  
 6)NOTE: PLEASE CORRELATE AHU'S OCP
 AND LOADS WITH MECH PLANS.
 PLEASE VERIFY OCP W/ LOADS.
  
 PLEASE SEE ANY OTHER COMMENTS FROM OTHER
 REVIEWS THAT MAY HAVE AN AFFECT ON
 ELECTRICAL PLANS.
  
 PLEASE REMOVE ALL OLD/VOIDED SHEETS AND
 ONLY INSERT NEW SHEETS INTO TWO COMPLETE
 SETS FOR REVIEW AND STAMPING.
 ONE SET OF OLD SHEETS MAY BE SUBMITTED
 FOR REFERENCE.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]