Plan Review Notes
Plan Review Notes For Permit 04041956
Permit Number 04041956
Review Stop E
Sequence Number 6
Notes
Date Text
2004-10-06 00:00:00********* UNSAT ***********
  
 1)NOTE: PLEASE SEE PLANS ARE NOW BEING
 SUBMITTED WITH A COMPLETELY NEW RISER
 DIAGRAM SHOWN???
 PLEASE SEE PLANS/FLOOR LAYOUT STILL SHOW
 'S METER/MAIN COMBO AS SHOWN ON PREVIOUS
 PLANS YET THIS DOES NOT CORRELATE WITH
 NEW RISER?
 PLEASE SEE MAINS ARE NOT NOT GROUPED AS
 REQUIRED PER 230.72??
  
 2)NOTE:PLEASE ALSO SEE EQUIPMENT GROUND-
 -ING CONDUCTORS ARE NOW BEING SHOWN
 BEFORE THE FIRST MEANS OF DISCONNECT.
 PLEASE SEE 250.6, 250.24 EQUIPMENT
 GROUNDING IS ONLY INSTALLED AFTER THE
 FIRST MEANS OF DISCONNECT.
  
 3)NOTE: PLEASE SEE 61G1-16.004 FOR
 ALL INFORMATION REQUIRED TO BE PRINTED
 ON TITLE BLOCK AS NOTED ON PREVIOUS
 REVIEW.
  
 **PLEASE SEE ONE SET OF EACH PLANS ARE
 NOW BEING RETAINED FOR FILE,AND POSSIBLE
 REVIEW BY THE BOARD OF ARCHITECTS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]