Plan Review Notes
Plan Review Notes For Permit 04041956
Permit Number 04041956
Review Stop E
Sequence Number 5
Notes
Date Text
2004-09-01 00:00:00*********** UNSAT ***************
  
 1)NOTE: PLEASE SEE MISSING GROUNDING
 SYSTEM AT DETACHED BLDG.
 NEC 250.32
  
 2)NOTE: PLEASE SEE MAIN HOUSE GROUNDING
 ELECTRODE SYSTEM SHOWS FOUN STEEL AGAIN.
 PLEASE VERIFY THIS FOR EXISTING DWELL-
 -ING?
 250.50
 NOT REQUIRED UNLESS SHOWN ON PLANS.
 INFORMATION WE WERE GIVEN, THIS IS AN
 EXSITING HOUSE.
  
 3)NOTE: PLEASE SEE FAC 61G1-16.004 FOR
 MISSING INFORMATION ON TITLE BLOCK.
  
 4)NOTE: PLEASE SEE WHITE-OUT ON PLANS
 ARE NOT PERMITTED.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  