| 2004-08-03 00:00:00 | *********** UNSAT 3RD REVIEW ********** |
| | |
| | PLEASE SEE SOME NOTES FROM PREVIOUS |
| | HAVE NOT BEEN ADDRESSED. |
| | |
| | 1)NOTE: PLEASE SEE PERMIT APPLICATION |
| | STILL ONLY REFERENCE ADDITION OF NEW |
| | BATH?? |
| | |
| | 2)NOTE: PLEASE SEE 210.52E PLANS STILL |
| | MISSING FRONT AND REAR RECEPTS. |
| | |
| | 3)NOTE: PLEASE SEE DETACHED BLDG IS |
| | STILL MISSING REQUIRED GRND ROD AND CWP |
| | FOR GROUNDING PER 250.32. |
| | |
| | 4)NOTE: PLEASE SEE GARAGE IS STILL |
| | MISSING REQUIRED GFI RECEPT PER 210.52G |
| | GARAGE NOW APPEARS TO HAVE A RECEPT |
| | ADDED FOR GDO, YET PANEL SCHEDULE DOES |
| | NOT REFLECT THIS?? REQUIRED TO BE A |
| | DEDICATED CIRCUIT. |
| | |
| | NEW COMMENTS DUE TO CHANGES IN PLANS |
| | ONCE MORE. |
| | |
| | 1)NOTE: PLEASE SEE MAIN HOUSE GROUNDING |
| | ELECTRODE SYSTEM IS NOW SHOWING FOOTER |
| | STEEL FOR AN ATTACHMENT ON AN EXISTING |
| | BLDG. PLEASE SEE 250.50, GRND RODS WILL |
| | BE REQUIRED. |
| | |
| | 2)NOTE: PLEASE SEE THE WATER HEATER |
| | WHICH WAS IN MAIN HOUSE ON PREVIOUS |
| | REVIEWS, HAS NOW BEEN MOVED TO DETACHED |
| | BLDG. PLEASE SEE WATER HEATER IS STILL |
| | SHOWN ON MAIN HOUSE PANEL SCHEDULE AND |
| | NOT ON PANEL AT DETACHED BLDG. |
| | |
| | |
| | PLEASE SEE NOTICE WAS GIVEN ON PREVIOUS |
| | REVIEW IN REFERENCE TO FS 553.80(2)(B) |
| | WITH RESPECT TO DESIGN PROFESSIONAL. |
| | A 4X FEE HAS NOW BEEN ACCESSED DUE TO |
| | CODE COMPLIANCE COMMENTS BEING REPEATED |
| | ON THE REVIEWS 3 OR MORE TIMES. |
| | BZ 244396 $240.00 |
| | THIS FEE IS REQUIRED TO BE PAID BEFORE |
| | PLANS MAY BE RE-SUBMITTED. |
| | ONE COPY OF EACH ELECTRICAL PLAN HAS NOW |
| | BEEN RETAINED FOR FILE AND POSSIBLE |
| | FURTHER ACTION TO BE TAKEN UP WITH |
| | THE BOARD. |
| | |