Plan Review Notes
Plan Review Notes For Permit 04041956
Permit Number 04041956
Review Stop E
Sequence Number 3
Notes
Date Text
2004-08-03 00:00:00*********** UNSAT 3RD REVIEW **********
  
 PLEASE SEE SOME NOTES FROM PREVIOUS
 HAVE NOT BEEN ADDRESSED.
  
 1)NOTE: PLEASE SEE PERMIT APPLICATION
 STILL ONLY REFERENCE ADDITION OF NEW
 BATH??
  
 2)NOTE: PLEASE SEE 210.52E PLANS STILL
 MISSING FRONT AND REAR RECEPTS.
  
 3)NOTE: PLEASE SEE DETACHED BLDG IS
 STILL MISSING REQUIRED GRND ROD AND CWP
 FOR GROUNDING PER 250.32.
  
 4)NOTE: PLEASE SEE GARAGE IS STILL
 MISSING REQUIRED GFI RECEPT PER 210.52G
 GARAGE NOW APPEARS TO HAVE A RECEPT
 ADDED FOR GDO, YET PANEL SCHEDULE DOES
 NOT REFLECT THIS?? REQUIRED TO BE A
 DEDICATED CIRCUIT.
  
 NEW COMMENTS DUE TO CHANGES IN PLANS
 ONCE MORE.
  
 1)NOTE: PLEASE SEE MAIN HOUSE GROUNDING
 ELECTRODE SYSTEM IS NOW SHOWING FOOTER
 STEEL FOR AN ATTACHMENT ON AN EXISTING
 BLDG. PLEASE SEE 250.50, GRND RODS WILL
 BE REQUIRED.
  
 2)NOTE: PLEASE SEE THE WATER HEATER
 WHICH WAS IN MAIN HOUSE ON PREVIOUS
 REVIEWS, HAS NOW BEEN MOVED TO DETACHED
 BLDG. PLEASE SEE WATER HEATER IS STILL
 SHOWN ON MAIN HOUSE PANEL SCHEDULE AND
 NOT ON PANEL AT DETACHED BLDG.
  
  
 PLEASE SEE NOTICE WAS GIVEN ON PREVIOUS
 REVIEW IN REFERENCE TO FS 553.80(2)(B)
 WITH RESPECT TO DESIGN PROFESSIONAL.
 A 4X FEE HAS NOW BEEN ACCESSED DUE TO
 CODE COMPLIANCE COMMENTS BEING REPEATED
 ON THE REVIEWS 3 OR MORE TIMES.
 BZ 244396 $240.00
 THIS FEE IS REQUIRED TO BE PAID BEFORE
 PLANS MAY BE RE-SUBMITTED.
 ONE COPY OF EACH ELECTRICAL PLAN HAS NOW
 BEEN RETAINED FOR FILE AND POSSIBLE
 FURTHER ACTION TO BE TAKEN UP WITH
 THE BOARD.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]