Plan Review Notes
Plan Review Notes For Permit 04041956
Permit Number 04041956
Review Stop E
Sequence Number 2
Notes
Date Text
2004-06-22 00:00:00*********** UNSAT *****************
  
 PLEASE SEE SOME NOTES AND REDLINED ITEMS
 FROM FIRST REVIEW WERE NOT ADDRESSED.
 PLANS ALSO HAVE CHANGES MADE FROM FIRST
 SET OF PLANS THAT NOW HAVE COMMENTS.
  
 1)NOTE: PLEASE SEE APPLICATION STILL
 CALLS OUT FOR REMODEL OF BATH?
 PLAN SHOWS COMPLETE REWIRE?
  
 2)NOTE: PLEASE SEE 250.32 FOR GROUNDING
 AT DETACHED BLDG.
  
 3)NOTE: PLEASE SEE SOME CONDUITS ARE
 \STILL MISSING EQUIPMENT GROUNDING
 CONDUCTORS. 250.110,250.122
 PLEASE NOW SEE AN EQUIPMENT GRND HAS
 BEEN ADDED TO RISE AHEAD OF METER AND
 FROM METER TO THE FIRST MEANS OF DISC.
 PLEASE SEE 250.24,250.6. THIS SHALL NOT
 BE INSTALLED.
  
 4)NOTE: PANEL AT MAIN HOUSE IS NOW BEING
 SHOWN AS "MCO"?PLEASE ALSO SEE WHAT
 APPEARS TO BE A MAIN DISC BEING ADDED
 AHEAD OF 200A PANEL?
 PLEASE SHOW ON PLANS AND CLARIFY IF
 PANEL IS NOW A "MLO" W/ A MAIN DISC
 OUTSIDE.? 215.5
  
 5)NOTE: PLEASE SEE SD'S STILL MISSING
 AT DEATCHED BLDG. THIS IS CONSIDERED
 AN ADAPTABLE SLEEPING AREA. SD'S ARE
 REQUIRED INSIDE AND OUTSIDE ROOM.
  
 6)NOTE: PLEASE SEE ORIG PLAN WAS RED-
 -LINED FOR 210.52E FOR MISSING FRONT AND
 REAR RECEPT(S).
  
 7)NOTE:PLEASE SEE KW RATING FOR A/C UNIT
 HAS NOW CHANGED TO 10KW. HOWEVER OCP
 HAS NOW DROPPED BACK DOWN TO 40A'S?
 PLEASE SEE 424.3B MIN 125%.
 PLEASE ALSO SEE AWG HAS NOW CHANGED FROM
 THE REQUIRED #6 AS SHOWN ON ORIG PLANS
 TO #8?310.16
  
 8)NOTE: PLEASE SEE PANEL SCHEDULE NOW
 HAS BEEN CHANGED TO SHOW SUB-FEEDERS AS
 #8'S, YET RISER STILL IS SHOWING #6'S.
 PLEASE CORRELATE.
  
 9)NOTE: PLEASE SEE RISER DIAGRAM NOW
 SHOWS OCP FOR A/C AHU. SHOWN AS 60A DISC
 W/30A OCP>?? PLEASE SEE NOTE 7).
 424.3B. 10KW. CONDUCTORS ON RISER HAVE
 NOW CHANGED ALSO.
  
 10)NOTE: PLEASE SEE PLANS SHOW A 50A
 DISC AT DETACHED BLDG AND RISER INDICATE
 -S 60A? PLEASE CORRELATE.
  
 11)NOTE: PLEASE SEE MISSING RECEPT IN
 GARAGE PER 210.52G AND RECEPT FOR 2'
 OF WALL IN MIDDLE BEDRM. 210.52
 NEW NOTE.
  
 12)NOTE: PLEASE SEE COPY OF FS 553.80(2)
 (B) ATTACHED. THIS IS A NOTICE GIVEN
 WITH RESPECT TO DESIGN PROFESSIONAL.
 THIS IS ONLY A NOTICEAT THIS TIME.
  
 PLEASE TAKE OUT AND REMOVE ALL OLD/
 VOIDED SHEETS. PLEASE ONLY INSERT NEW
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. ONE SET OF OLD SHEETS
 MAY BE SUBMITTED FOR REFERENCE ONLY.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]