| 2004-06-22 00:00:00 | *********** UNSAT ***************** |
| | |
| | PLEASE SEE SOME NOTES AND REDLINED ITEMS |
| | FROM FIRST REVIEW WERE NOT ADDRESSED. |
| | PLANS ALSO HAVE CHANGES MADE FROM FIRST |
| | SET OF PLANS THAT NOW HAVE COMMENTS. |
| | |
| | 1)NOTE: PLEASE SEE APPLICATION STILL |
| | CALLS OUT FOR REMODEL OF BATH? |
| | PLAN SHOWS COMPLETE REWIRE? |
| | |
| | 2)NOTE: PLEASE SEE 250.32 FOR GROUNDING |
| | AT DETACHED BLDG. |
| | |
| | 3)NOTE: PLEASE SEE SOME CONDUITS ARE |
| | \STILL MISSING EQUIPMENT GROUNDING |
| | CONDUCTORS. 250.110,250.122 |
| | PLEASE NOW SEE AN EQUIPMENT GRND HAS |
| | BEEN ADDED TO RISE AHEAD OF METER AND |
| | FROM METER TO THE FIRST MEANS OF DISC. |
| | PLEASE SEE 250.24,250.6. THIS SHALL NOT |
| | BE INSTALLED. |
| | |
| | 4)NOTE: PANEL AT MAIN HOUSE IS NOW BEING |
| | SHOWN AS "MCO"?PLEASE ALSO SEE WHAT |
| | APPEARS TO BE A MAIN DISC BEING ADDED |
| | AHEAD OF 200A PANEL? |
| | PLEASE SHOW ON PLANS AND CLARIFY IF |
| | PANEL IS NOW A "MLO" W/ A MAIN DISC |
| | OUTSIDE.? 215.5 |
| | |
| | 5)NOTE: PLEASE SEE SD'S STILL MISSING |
| | AT DEATCHED BLDG. THIS IS CONSIDERED |
| | AN ADAPTABLE SLEEPING AREA. SD'S ARE |
| | REQUIRED INSIDE AND OUTSIDE ROOM. |
| | |
| | 6)NOTE: PLEASE SEE ORIG PLAN WAS RED- |
| | -LINED FOR 210.52E FOR MISSING FRONT AND |
| | REAR RECEPT(S). |
| | |
| | 7)NOTE:PLEASE SEE KW RATING FOR A/C UNIT |
| | HAS NOW CHANGED TO 10KW. HOWEVER OCP |
| | HAS NOW DROPPED BACK DOWN TO 40A'S? |
| | PLEASE SEE 424.3B MIN 125%. |
| | PLEASE ALSO SEE AWG HAS NOW CHANGED FROM |
| | THE REQUIRED #6 AS SHOWN ON ORIG PLANS |
| | TO #8?310.16 |
| | |
| | 8)NOTE: PLEASE SEE PANEL SCHEDULE NOW |
| | HAS BEEN CHANGED TO SHOW SUB-FEEDERS AS |
| | #8'S, YET RISER STILL IS SHOWING #6'S. |
| | PLEASE CORRELATE. |
| | |
| | 9)NOTE: PLEASE SEE RISER DIAGRAM NOW |
| | SHOWS OCP FOR A/C AHU. SHOWN AS 60A DISC |
| | W/30A OCP>?? PLEASE SEE NOTE 7). |
| | 424.3B. 10KW. CONDUCTORS ON RISER HAVE |
| | NOW CHANGED ALSO. |
| | |
| | 10)NOTE: PLEASE SEE PLANS SHOW A 50A |
| | DISC AT DETACHED BLDG AND RISER INDICATE |
| | -S 60A? PLEASE CORRELATE. |
| | |
| | 11)NOTE: PLEASE SEE MISSING RECEPT IN |
| | GARAGE PER 210.52G AND RECEPT FOR 2' |
| | OF WALL IN MIDDLE BEDRM. 210.52 |
| | NEW NOTE. |
| | |
| | 12)NOTE: PLEASE SEE COPY OF FS 553.80(2) |
| | (B) ATTACHED. THIS IS A NOTICE GIVEN |
| | WITH RESPECT TO DESIGN PROFESSIONAL. |
| | THIS IS ONLY A NOTICEAT THIS TIME. |
| | |
| | PLEASE TAKE OUT AND REMOVE ALL OLD/ |
| | VOIDED SHEETS. PLEASE ONLY INSERT NEW |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. ONE SET OF OLD SHEETS |
| | MAY BE SUBMITTED FOR REFERENCE ONLY. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |