| Date |
Text |
| 2004-05-04 00:00:00 | *************** UNSAT ************* |
| | |
| | 1)NOTE: PLEASE SEE APPLICATION WAS |
| | SUBMITTED FOR REMODEL OF BATH YET PLANS |
| | SHOW COMPLETE REMOD FOR ELECTRICAL ?? |
| | PLEASE CLARIFY.??? |
| | |
| | 2)NOTE: PLEASE SEE FAC 61G1-16.004 FOR |
| | ALL LICENSE #'S REQ'D ON TITLE BLOCK. |
| | PLEASE ALSO SEE FS 481.219 FOR REQ'D |
| | CERTIFICATE OF AUTHORIZATION #. |
| | THIS IS FOR ALL TRADES AND ALL SHEETS |
| | WEATHER OR NOT COMMENT IS MADE FROM |
| | OTHER REVIEWERS. |
| | |
| | REVIEW FOR ELECTRICAL CODE COMPLIANCE |
| | FOR NEW ELECTRICAL AS SHOWN. |
| | |
| | 1)NOTE: PLEASE SHOW ALL A/C EQUIPMENT |
| | AND DISC'S PER 440.11, RECEPTS PER |
| | 210.63/ 210.70 |
| | |
| | 2)NOTE: PLEASE SEE 220 FOR LOAD CALCU- |
| | -LATIONS. PLEASE SEE 220.16, 220.18 |
| | |
| | 3)NOTE: PLEASE SEE NFPA-72 FOR REQ'D |
| | SD'S MISSING. |
| | |
| | 4)NOTE: PLEASE SEE 210.8A6 FOR GFI |
| | PROTECTION REQ'D. |
| | |
| | 5)NOTE: PLEASE SEE 424.3B FOR OCP |
| | SHOWN FOR AHU. 60A FOR 5KW?? |
| | |
| | 6)NOTE: PLEASE SEE 225.31,250.32 FOR |
| | DETACHED BLDG. |
| | |
| | 7)NOTE: PLEASE SEE 250.110, 250.122 FOR |
| | MISSING EQUIPMENT GROUNDING CONDUCTORS |
| | ON RISER DIAGRAM. |
| | |
| | 8)NOTE: PLEASE VERIFY COMPLIANCE W/ |
| | 230.70 FOR MORE THAN 8' OF UNPROTECTED |
| | CONDUCTORS INSIDE HOUSE FROM METER? |
| | |
| | 9)NOTE: PLEASE SUBMIT AIC RATINGS FOR |
| | ALL NEW SERVICE EQUIPMENT BEING INSTALL- |
| | ED. MAINS/BRKRS AND PANELS ARE ALL TO BE |
| | RATED FOR THE AVAILABLE FAULT CURRENT. |
| | PER 110.9/215.5 |
| | |
| | 10)NOTE: PLEASE LIST THE REQ'D ARC |
| | FAULT PROTECTED CURCUIT(S) ON PANEL |
| | SCHEDULE. PLEASE SEE THAT ALL "OUTLETS" |
| | IN BEDROOMS ARE TO BE PROTECTED , |
| | INCLUDING, LTS, RECEPTS, SD'S ETC. |
| | 210.12, 2002 NEC |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CITY OF WEST PALM BEACH |
| | CONSTUCTION SERVICES DEPT. |
| | 561-805-6717 |
| | [email protected] |