2004-05-04 00:00:00*************** UNSAT *************
  
 1)NOTE: PLEASE SEE APPLICATION WAS
 SUBMITTED FOR REMODEL OF BATH YET PLANS
 SHOW COMPLETE REMOD FOR ELECTRICAL ??
 PLEASE CLARIFY.???
  
 2)NOTE: PLEASE SEE FAC 61G1-16.004 FOR
 ALL LICENSE #'S REQ'D ON TITLE BLOCK.
 PLEASE ALSO SEE FS 481.219 FOR REQ'D
 CERTIFICATE OF AUTHORIZATION #.
 THIS IS FOR ALL TRADES AND ALL SHEETS
 WEATHER OR NOT COMMENT IS MADE FROM
 OTHER REVIEWERS.
  
 REVIEW FOR ELECTRICAL CODE COMPLIANCE
 FOR NEW ELECTRICAL AS SHOWN.
  
 1)NOTE: PLEASE SHOW ALL A/C EQUIPMENT
 AND DISC'S PER 440.11, RECEPTS PER
 210.63/ 210.70
  
 2)NOTE: PLEASE SEE 220 FOR LOAD CALCU-
 -LATIONS. PLEASE SEE 220.16, 220.18
  
 3)NOTE: PLEASE SEE NFPA-72 FOR REQ'D
 SD'S MISSING.
  
 4)NOTE: PLEASE SEE 210.8A6 FOR GFI
 PROTECTION REQ'D.
  
 5)NOTE: PLEASE SEE 424.3B FOR OCP
 SHOWN FOR AHU. 60A FOR 5KW??
  
 6)NOTE: PLEASE SEE 225.31,250.32 FOR
 DETACHED BLDG.
  
 7)NOTE: PLEASE SEE 250.110, 250.122 FOR
 MISSING EQUIPMENT GROUNDING CONDUCTORS
 ON RISER DIAGRAM.
  
 8)NOTE: PLEASE VERIFY COMPLIANCE W/
 230.70 FOR MORE THAN 8' OF UNPROTECTED
 CONDUCTORS INSIDE HOUSE FROM METER?
  
 9)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW SERVICE EQUIPMENT BEING INSTALL-
 ED. MAINS/BRKRS AND PANELS ARE ALL TO BE
 RATED FOR THE AVAILABLE FAULT CURRENT.
 PER 110.9/215.5
  
 10)NOTE: PLEASE LIST THE REQ'D ARC
 FAULT PROTECTED CURCUIT(S) ON PANEL
 SCHEDULE. PLEASE SEE THAT ALL "OUTLETS"
 IN BEDROOMS ARE TO BE PROTECTED ,
 INCLUDING, LTS, RECEPTS, SD'S ETC.
 210.12, 2002 NEC
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]