2004-05-13 00:00:00BUILDING PLAN REVIEW
 PERMIT: 04041936
 ADD: 525 S FLAGLER DR/ 27B
 CONT: CONSTRUCTION CONNENCTION
 TEL: (772)263-3325
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 1ST REVIEW
 ACTION: DENIED
  
 1) PROVIDE NOC RECORDED WITH THE CLERK
 OF COURT BEFORE A PERMIT CAN BE ISSUED.
  
 2)ALL INFORMATION, DRAWINGS, SPECIF-
 ICATIONS AND ACCOMPANYING DATA SHALL
 BEAR THE NAME AND SIGNATURE OF THE
 PERSON RESPONSIBLE FOR THE DESIGN.
 CITY AMENDMENTS 104.2.1
  
 3) TABLE 803.3 MINIMUM INTERIOR FINISH
 CLASSIFICATION; PROVIDE INFORMATION
 BASED ON INTERIOR FINISH REQUIREMENTS
 BASED ON OCCUPANCY
  
 4)FL BLD CODE 104.2.1.2
 ADDITIONAL INFORMATION REQUIRED,
 WHAT TYPE OF MATERIAL WILL THE CROWN
 MOLDING BE MADE FROM?
 803.4 FOAM PLASTICS SHALL NOT BE USED AS
 INTERIOR FINISH.
 EXCEPTION
 A) THE MINIMUM DENSITY IS 20 LB/CU FT
 B) THE MAXIMUM THICKNESS IS 1/2 " AND
 THE MAXIMUM WIDTH IS 4".
 C) THE TRIM CONSTITUTES NO MORE THAN
 10% OF THE AREA OF WALL OR CEILING.
 D)THE FLAMESPREAD RATING DOES NOT EXCEED
 75 WHEN TESTED PER ASTM E 84. THE SMOKE
 DEVELOPMENT RATING IS NOT LIMITED.
  
 BUILDING PLAN REVIEW