| Plan Review Notes For Permit 04041936 |
| Permit Number |
04041936 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2004-05-13 00:00:00 | BUILDING PLAN REVIEW | | | PERMIT: 04041936 | | | ADD: 525 S FLAGLER DR/ 27B | | | CONT: CONSTRUCTION CONNENCTION | | | TEL: (772)263-3325 | | | FL BLD CODE= 2001 FLORIDA BUILDING CODE | | | | | | 1ST REVIEW | | | ACTION: DENIED | | | | | | 1) PROVIDE NOC RECORDED WITH THE CLERK | | | OF COURT BEFORE A PERMIT CAN BE ISSUED. | | | | | | 2)ALL INFORMATION, DRAWINGS, SPECIF- | | | ICATIONS AND ACCOMPANYING DATA SHALL | | | BEAR THE NAME AND SIGNATURE OF THE | | | PERSON RESPONSIBLE FOR THE DESIGN. | | | CITY AMENDMENTS 104.2.1 | | | | | | 3) TABLE 803.3 MINIMUM INTERIOR FINISH | | | CLASSIFICATION; PROVIDE INFORMATION | | | BASED ON INTERIOR FINISH REQUIREMENTS | | | BASED ON OCCUPANCY | | | | | | 4)FL BLD CODE 104.2.1.2 | | | ADDITIONAL INFORMATION REQUIRED, | | | WHAT TYPE OF MATERIAL WILL THE CROWN | | | MOLDING BE MADE FROM? | | | 803.4 FOAM PLASTICS SHALL NOT BE USED AS | | | INTERIOR FINISH. | | | EXCEPTION | | | A) THE MINIMUM DENSITY IS 20 LB/CU FT | | | B) THE MAXIMUM THICKNESS IS 1/2 " AND | | | THE MAXIMUM WIDTH IS 4". | | | C) THE TRIM CONSTITUTES NO MORE THAN | | | 10% OF THE AREA OF WALL OR CEILING. | | | D)THE FLAMESPREAD RATING DOES NOT EXCEED | | | 75 WHEN TESTED PER ASTM E 84. THE SMOKE | | | DEVELOPMENT RATING IS NOT LIMITED. | | | | | | BUILDING PLAN REVIEW | | | JIM WITMER | | | TEL: (561)805-6715 | | | FAX: (561)659-8026 |
|