Plan Review Notes
Plan Review Notes For Permit 04041914
Permit Number 04041914
Review Stop P
Sequence Number 1
Notes
Date Text
2004-05-19 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
  
 1) SHT A6 THE SANITARY RISER DIAGRAM
 DOES NOT REFLECT THE FLOOR PLAN, NOR
 DOES IT MEET CODE REQUIREMENTS.
 A) THE RISER IS REVERSE FROM THE FLOOR
 PLAN. SUBMIT A RISER THAT REFLECTS THE
 FLOOR PLAN. SECTION 104.2.1.
 B) PROPERLY IDENTIFY ALL FIXTURES ON
 THE RISER DIAGRAM. SECTION 104.2.1.
 C) SIZE ALL PIPES IN SYSTEM. TABLES
 709.1, 710.1(1) & 710.1(2) AND SECTION
 104.2.1.
 D) CLEAN OUT REQUIRED 4' ABOVE THE
 FLOOR AT WASH MACHINE. SECTION 708.10.
 E) STAND PIPE REQUIRED AT THE WASH
 MACHINE. SECTIONS 802.4 & 1002.1.
 F) THE WASH MACHINE SHALL CONNECT DOWN-
 STREAM OF THE LAUNDRY SINK ON THE STACK.
 SECTION 706.3.
 G) THE LAUNDRY SINK AND WASH MACHINE
 SHALL DISCHARGE DOWNSTREAM OF THE WET-
 VENTED HORIZONTAL DRAIN FOR BATH #2.
 SECTION 909.1.
 H) THE WATER CLOSET AND SHOWER ARE NOT
 VENTED PROPERLY IN BATH #2. SECTIONS
 901.2.1 & 909.1.
 I) THE BIDET IS NOT VENTED IN THE MAST-
 ER BATH. SECTION 901.2.1.
 J) THE CABANA BATH SHOWS A SHOWER ON
 THE RISER DIAGRAM THAT IS NOT SHOWN ON
 THE FLOOR PLAN, AND THE RISER SHOWS THE
 CABANA BATH ON THE WRONG SIDE OF THE
 HOUSE. SECTION 104.2.1.
 2) THE SANITARY RISER DIAGRAM SHALL RE-
 FLECT THE INSTALLATION OF THE PIPE AND
 I SUGGEST THAT THE PLUMBING CONTRACTOR
 BE CONTACTED SO HE CAN INDICATE HOW THE
 PIPING WILL BE INSTALLED.
  