| 2004-05-19 00:00:00 | DENIED |
| | REFERENCE: FBC-2001 PLUMBING |
| | FBC-2001 CHAPTER 1 |
| | |
| | 1) SHT A6 THE SANITARY RISER DIAGRAM |
| | DOES NOT REFLECT THE FLOOR PLAN, NOR |
| | DOES IT MEET CODE REQUIREMENTS. |
| | A) THE RISER IS REVERSE FROM THE FLOOR |
| | PLAN. SUBMIT A RISER THAT REFLECTS THE |
| | FLOOR PLAN. SECTION 104.2.1. |
| | B) PROPERLY IDENTIFY ALL FIXTURES ON |
| | THE RISER DIAGRAM. SECTION 104.2.1. |
| | C) SIZE ALL PIPES IN SYSTEM. TABLES |
| | 709.1, 710.1(1) & 710.1(2) AND SECTION |
| | 104.2.1. |
| | D) CLEAN OUT REQUIRED 4' ABOVE THE |
| | FLOOR AT WASH MACHINE. SECTION 708.10. |
| | E) STAND PIPE REQUIRED AT THE WASH |
| | MACHINE. SECTIONS 802.4 & 1002.1. |
| | F) THE WASH MACHINE SHALL CONNECT DOWN- |
| | STREAM OF THE LAUNDRY SINK ON THE STACK. |
| | SECTION 706.3. |
| | G) THE LAUNDRY SINK AND WASH MACHINE |
| | SHALL DISCHARGE DOWNSTREAM OF THE WET- |
| | VENTED HORIZONTAL DRAIN FOR BATH #2. |
| | SECTION 909.1. |
| | H) THE WATER CLOSET AND SHOWER ARE NOT |
| | VENTED PROPERLY IN BATH #2. SECTIONS |
| | 901.2.1 & 909.1. |
| | I) THE BIDET IS NOT VENTED IN THE MAST- |
| | ER BATH. SECTION 901.2.1. |
| | J) THE CABANA BATH SHOWS A SHOWER ON |
| | THE RISER DIAGRAM THAT IS NOT SHOWN ON |
| | THE FLOOR PLAN, AND THE RISER SHOWS THE |
| | CABANA BATH ON THE WRONG SIDE OF THE |
| | HOUSE. SECTION 104.2.1. |
| | 2) THE SANITARY RISER DIAGRAM SHALL RE- |
| | FLECT THE INSTALLATION OF THE PIPE AND |
| | I SUGGEST THAT THE PLUMBING CONTRACTOR |
| | BE CONTACTED SO HE CAN INDICATE HOW THE |
| | PIPING WILL BE INSTALLED. |
| | |
| | REVIEW BY KEN STEVENS |