Plan Review Notes
Plan Review Notes For Permit 04041907
Permit Number 04041907
Review Stop P
Sequence Number 2
Notes
Date Text
2004-05-28 00:00:00REVISION OK - CHANGED 3/4" TO 1/2" CSST
 TO 60K BTU RANGE
  
  
  
 PER N. MELICK MANUFACTURE INFO
 NOT REQUIRED FOR 1 & 2 FAMILY HOMES.
 JULY 17, 2002 OFFICAL INTERPRETATION.
 THE FIELD INSPECTOR SHALL VERIFY THE
 INSTALLED EQUIPMENT INPUT DOES NOT EX-
 CEED THE PIPE SIZING.
  
 IF DRYER ROOM IS A CONFINED SPACE,
 OPENINGS REQUIRED PER SECTION 304.3.1 0R
 SECTION 304.3.2 SHALL BE INSTALLED.
 MINIMUM 1,100 CUBIC FEET REQUIRED.
  
  
  
  
  
  
  
  
  