Plan Review Notes
Plan Review Notes For Permit 04041900
Permit Number 04041900
Review Stop P
Sequence Number 2
Notes
Date Text
2004-06-16 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
 FBC-2001 FUEL GAS
  
 1) PLANS ROUTED TO DBPR HOTEL AND REST-
 URANT. TWO COPIES ARE REQUIRED WITH THE
 WORKSHEETS ONLY ATTACHED. SHEETS SHALL
 BE PART OF THE PLANS SUBMITTED AND ALL
 OTHER "K" SHEETS REMOVED. SEC. 104.2.1
 ONLY ONE SET HAS BEEN STAMPED BY HOTEL
 AND RESTURANT DIVISION.
 2) FROM PREVIOUS REVIEW: #4 SHEET C-4.0
 NO CONNECTION TO FLOOR DRAIN FOR THE RE-
 FUSE ENCLOSURE IS SHOWN. THIS SHALL BE
 CONNECTED TO THE GREASE LINE. RESPONSE
 NOTED, BUT SHT PS-1.0 PLUMBING SITE PLAN
 DOES NOT SHOW A CONNECTION. PLEASE INDI-
 CATE WHERE THIS IS SHOWN. SEC 104.2.1
 3) PER TABLE 1106.3 THE MAXIMUM SQUARE
 FEET OF RAIN WATER FOR A 3" PIPE @ 1/2"
 PER FT. IS 1,461. PLAN INDICATES THAT
 THE AREA FOR EACH ROOF DRAIN IS 1,468.
 4" PIPE SHALL BE REQUIRED FOR THE HORIZ-
 ONTAL STORM PIPING.
 4) GAS RISER DIAGRAM DOES NOT SHOW PIP-
 ING TO THE METER. SHOW PIPING TO THE GAS
 METER AND THE LENGTH OF ALL CUT SECTIONS
 TO THE METER.
 - SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY (METER) TO THE MOST REMOTE OUT-
 LET. RESPONSE NOTED, BUT METER NOT SHOWN
 ON RISER DIAGRAM THUS NO MEASURMENT TO
 METER SHOWN.
 - SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE FBC-
 2001 FUEL GAS CODE SEC 402.2. RESPONSE
 NOTED, BUT NO SHEETS WERE FOUND WITH
 PLANS. PLEASE CLARIFY.
 NEW COMMENT:***********
 1B) EMERGENCY HOOD SHUT DOWN SHUT OFF
 VALVE TO BE BELOW CEILING. MANUAL SHUT
 OFF VALVE TO BE UPSTREAM. UNION TO BE
 DOWN STREAM OF MANUAL VALVE.
  
 REVIEW BY KEN STEVENS