| Date |
Text |
| 2004-06-16 00:00:00 | DENIED |
| | REFERENCE: FBC-2001 PLUMBING |
| | FBC-2001 CHAPTER 1 |
| | FBC-2001 FUEL GAS |
| | |
| | 1) PLANS ROUTED TO DBPR HOTEL AND REST- |
| | URANT. TWO COPIES ARE REQUIRED WITH THE |
| | WORKSHEETS ONLY ATTACHED. SHEETS SHALL |
| | BE PART OF THE PLANS SUBMITTED AND ALL |
| | OTHER "K" SHEETS REMOVED. SEC. 104.2.1 |
| | ONLY ONE SET HAS BEEN STAMPED BY HOTEL |
| | AND RESTURANT DIVISION. |
| | 2) FROM PREVIOUS REVIEW: #4 SHEET C-4.0 |
| | NO CONNECTION TO FLOOR DRAIN FOR THE RE- |
| | FUSE ENCLOSURE IS SHOWN. THIS SHALL BE |
| | CONNECTED TO THE GREASE LINE. RESPONSE |
| | NOTED, BUT SHT PS-1.0 PLUMBING SITE PLAN |
| | DOES NOT SHOW A CONNECTION. PLEASE INDI- |
| | CATE WHERE THIS IS SHOWN. SEC 104.2.1 |
| | 3) PER TABLE 1106.3 THE MAXIMUM SQUARE |
| | FEET OF RAIN WATER FOR A 3" PIPE @ 1/2" |
| | PER FT. IS 1,461. PLAN INDICATES THAT |
| | THE AREA FOR EACH ROOF DRAIN IS 1,468. |
| | 4" PIPE SHALL BE REQUIRED FOR THE HORIZ- |
| | ONTAL STORM PIPING. |
| | 4) GAS RISER DIAGRAM DOES NOT SHOW PIP- |
| | ING TO THE METER. SHOW PIPING TO THE GAS |
| | METER AND THE LENGTH OF ALL CUT SECTIONS |
| | TO THE METER. |
| | - SHOW THE DISTANCE FROM THE POINT OF |
| | DELIVERY (METER) TO THE MOST REMOTE OUT- |
| | LET. RESPONSE NOTED, BUT METER NOT SHOWN |
| | ON RISER DIAGRAM THUS NO MEASURMENT TO |
| | METER SHOWN. |
| | - SUBMIT MANUFACTURE SHEETS FOR ALL GAS |
| | EQUIPMENT TO VERIFY COMPLIANCE WITH |
| | STANDARDS NFPA 54, NFPA 58, AND THE FBC- |
| | 2001 FUEL GAS CODE SEC 402.2. RESPONSE |
| | NOTED, BUT NO SHEETS WERE FOUND WITH |
| | PLANS. PLEASE CLARIFY. |
| | NEW COMMENT:*********** |
| | 1B) EMERGENCY HOOD SHUT DOWN SHUT OFF |
| | VALVE TO BE BELOW CEILING. MANUAL SHUT |
| | OFF VALVE TO BE UPSTREAM. UNION TO BE |
| | DOWN STREAM OF MANUAL VALVE. |
| | |
| | REVIEW BY KEN STEVENS |
| | (561) 805-6721 |
| | FAX (561) 653-2692 |
| | E-MAIL [email protected] |