| Date |
Text |
| 2004-06-15 00:00:00 | *********** UNSAT *********** |
| | |
| | PLEASE SEE SOME COMMENTS FROM FIRST |
| | REVIEW STILL NEED TO BE ADDRESSED. |
| | PLEASE SEE NOTES BELOW. |
| | |
| | NOTE #1 OK. |
| | |
| | NOTE #2 NOTE: |
| | PLEASE SEE WIND LOADING REPORT WILL |
| | BE REQUIRED TO BE REVIEWED BY BLDG PLAN |
| | REVIEW. THIS REPORT WILL ALSO BE |
| | REQUIRED TO BE SIGNED,DATED AND SEALED |
| | BY A FLORIDA PE. REPORT WILL REQUIRE |
| | TITLE BLOCK AND INFORMATION AS SET FORTH |
| | UNDER FAC 61G15-23.002/ FS 471.025 |
| | PLEASE SEE INFORMATION FOUND ON ES-2.0 |
| | DOES NOT SEEM TO CORRELATE WITH # OF |
| | FIXTURES, TYPE OF FIXTURES AS SHOWN |
| | ON REPORT AND PLANS. |
| | |
| | NOTE #3 NOTE: PLEASE SEE PANEL SCHEDULE |
| | INFORMATION FOR MDP INDICATES PANEL AS |
| | MLO. A SHUNT TRIP SHALL NOT BE CONSIDER- |
| | -ED A "MEANS OF DISCONNECT". 230.76,230- |
| | -79. |
| | PLEASE SEE MDP ALSO SHOWS MORE THAN |
| | 6 MEANS OF DISC. PANEL SCHEDULE SHOWS |
| | 18 SPACES CAPABLE OF HAVING 18 MEANS |
| | OF DISCONNECT.230.71 |
| | |
| | NOTE #4 NOTE: PLANS STILL NOTE, "WHERE |
| | 2002 NEC IS IN EFFECT" PLEASE NOTE: |
| | PLANS PER 2002 NEC. |
| | PLEASE ALSO SEE OPT LOAD SUMMARY, PLANS |
| | STILL NOTE 96 AND 99 NEC.SEE ONE SET |
| | HAS BEEN REDLINED FOR THIS. |
| | |
| | PLEASE SEE PLANS ARE ONLY IN FOR "PLAN |
| | REVIEW" AND NOT FOR PERMIT. |
| | |
| | PLEASE REMOVE ALL OLD/VOIDED SHEETS AND |
| | ONLY INSERT NEW SHEETS FOR REVIEW AND |
| | STAMPING. ONE SET OF OLD/VOIDED SHEETS |
| | MAY BE SUBMITTED FOR REFERENCE ONLY, |
| | WHICH MAY BE REQUIRED BY SOME REVIEWERS. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CITY OF WEST PALM BEACH |
| | CONSTUCTION SERVICES DEPT. |
| | 561-805-6717 |
| | [email protected] |