Plan Review Notes
Plan Review Notes For Permit 04041900
Permit Number 04041900
Review Stop P
Sequence Number 1
Notes
Date Text
2004-05-15 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 FUEL GAS
 FBC-2001 CHAPTER 1
 FBC-2001 CHAPTER 11
 WPC CITY CODE
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1) PLANS SHALL BE ROUTED TO THE DEPT.
 BUSINESS REGULATION HOTEL & RESTURANT
 DIVISION FOR REVIEW PRIOR TO RESUBMITT-
 ING FOR REVIEW. PLANS SHALL BE STAMPED
 AND WORKSHEETS FROM DBPR ATTACHED TO
 EACH SET OF PLANS. SEC. 101.4.7
 2) CONTACT RODNEY COMPO, ENVIRONMENTAL
 COMPLIANCE FOR SIZING OF GREASE INTER-
 CEPTOR. WASTE ORD. #2938-96. (561) 837-
 4074.
 3) SEPARATE PERMITS REQUIRED FOR GAS,
 IRRIGATION, AND GREASE INTERCEPTOR.
 4) SHT C-4.0 NO CONNECTION TO FLOOR
 DRAIN FOR THE REFUSE ENCLOSURE IS SHOWN.
 THIS SHALL BE TIED INTO THE GREASE LINE.
 5) SHTS A-1.7 & P-2 NOTE STATES "CONDEN-
 SATE TO MOP SINK BELOW". THIS IS NOT
 APPROVED. CONDENSATE SHALL DRAIN SEPAR-
 ATELY OUT OF THE BLDG. TO A CATCH BASIN,
 A STORM LINE, OR APPROVED DRYWELL MIN.
 1' FROM STRUCTURAL SIDEWALL. CITY CODE
 SECTION 90-125(5).
 6) SHT P-2 CONDENSATE LINE FOR FREEZER/
 COOLER. A SEPARATE TRAP REQUIRED FOR
 EACH UNIT AND NO DOUBLE TRAPPING. SEC
 1002.1 - TRAP OUTSIDE COOLER TO BE RE-
 MOVED.
 7) SHT P-2 KEY NOTES #3, FLOOR DRAIN NOT
 AN APPROVED INDIRECT WASTE INTERCEPTOR.
 SEE SECTIONS 802.3 & 802.3.2, FLOOR SINK
 OR HUB DRAIN REQUIRED.
 8) SHT P-4 MORE INFORMATION ON PIPE SUP-
 PORT ON ROOF REQUIRED. INDICATE HOW SUP-
 PORTS WILL BE FASTENED TO THE ROOF. SHOW
 HOW SUPPORTS WILL BE ABLE TO WITHSTAND
 THE 140 MPH WIND LOADS.
 9) SHT P-5 WATER RISER DIAGRAM, WATER
 HAMMER ARRESTORS SHALL BE LOCATED NEAR
 THE FIXTURES IN AN "EFFECTIVE RANGE" NOT
 IN THE CEILING AS SHOWN. PDI-WH 201 AND
 MANUF. INSTALL. INSTRUCTIONS. - BALL
 CHECKS AT MOP SINK AND CAN WASH SHALL BE
 ACCESSIBLE.
 10) P-6 FIXTURE CONNECTION SHEDULE #36
 CATALOG INDICATES D50-064 IS A FLOOR
 DRAIN WHICH IS NOT AN APPROVED INDIRECT
 WASTE RECEPTOR. SEC 802.3 & 802.3.2.
 11) WATER FILTER SHALL BE NSF APPROVED
 PER SECTION 611.1. SUBMIT MANUF. SPECI-
 FICATION SHEETS.
 12) SHT P-7 PLUMBING SPECIFICATIONS PART
 3 - #7 PIPING SUPPORT SHALL BE PER TABLE
 308.5.
 13) SUBMIT CALCULATIONS FOR PRIMARY AND
 SECONDARY ROOF DRAINS PER SECTIONS 1106
 AND 1107 AND ALL ALL SUBSECTIONS. SHOW
 SQUARE FOOTAGE OF ROOF AND SHOW 1/2 AREA
 OF ALL VERTICAL WALLS INCLUDING PARAPETS
 BEING ADDED TO ROOF S.F.
 14) RAIN WATER SHALL DISCHARGE A MINIMUM
 OF 1 FOOR FROM THE SIDE WALL OF THE
 STRUCTURE PER SECTION 1503.4.4
 15) THE FOLLOWING INFORMATION IS REQUIR-
 ED FOR GAS PERMIT,
 A. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2001
 FUEL GAS CODE.
 B. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2001 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES (A)(3).
 C. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2001 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI.
 MINIMUM 1/2 LB SYSTEM SUPPLIED.
 D. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2001 FUEL GAS CODE SEC 402.2
 ****************************************
 A PROFESSIONAL ENGINEER SHALL SIGN HIS
 NAME AND AFFIX HIS SEAL TO ALL PLANS,
 SPECIFICATIONS, REPORTS AND FINAL BID
 DOCUMENTS PROVIDED TO THE OWNER OR THE
 OWNER'S REPRESENTATIVE, OR OTHER DOCU-
 MENTS PREPARED OR ISSUED BY SAID REGIS-
 TRANT AND BEING FILED FOR PUBLIC RECORD.
 THE DATE THAT THE SIGNATURE AND SEAL IS
 AFFIXED AS PROVIDED HEREIN SHALL BE EN-
 TERED ON SAID PLANS, SPECIFICATIONS, RE-
 PORTS, OR OTHER DOCUMENTS IMMEDIATELY
 UNDER THE SIGNATURE OF THE PROFESSIONAL
 ENGINEER, FAC 61G15-23.002(1)
 FS 471.025
 EACH SHEET OF PLANS AND PRINTS WHICH
 MUST BE SEALED UNDER THE PROVISIONS OF
 CHAPTER 471 SHALL BE SEALED, SIGNED AND
 DATED BY THE PROFESSIONAL ENGINEER IN
 RESPONSIBLE CHARGE. FAC 61G15-23.002(2)
 FS 471.025
 ENGINEERS SHALL LEGIBLY INDICATE THEIR
 NAME, ADDRESS AND LICENSE NUMBER ON EACH
 SHEET. IF PRACTICING THROUGH A DULY
 AUTHORIZED ENGINEERING BUSINESS, ENGIN-
 EERS, ENGINEERS SHALL LEGIBLY INDICATE
 THEIR NAME AND LICENSE NUMBER, AS WELL
 AS, THE NAME, ADDRESS AND CERTIFICATE OF
 AUTHORIZATION NUMBER OF THE ENGINEERING
 BUSINESS ON EACH SHEET. A TITLE BLOCK
 WILL SATISFY THIS REQUIREMENT. FAC
 61G15-23.002(2) - FS 471.025
 ****************************************
 <<<<<<<<>>>>>>>
 PLEASE CLEARLY INDICATE THE REVISION AND
 REMOVE AND REPLACE ANY PAGES AS NECESS-
 ARY. SUBMIT (1) SET OF OLD DRAWINGS WITH
 THE PLANS WHEN RESUBMITTING PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN
 BE FOUND, WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 REVIEW BY KEN STEVENS