| 2004-05-15 00:00:00 | DENIED |
| | REFERENCE: FBC-2001 PLUMBING |
| | FBC-2001 FUEL GAS |
| | FBC-2001 CHAPTER 1 |
| | FBC-2001 CHAPTER 11 |
| | WPC CITY CODE |
| | FLORIDA ADMINISTRATIVE CODE |
| | FLORIDA STATUTES |
| | |
| | 1) PLANS SHALL BE ROUTED TO THE DEPT. |
| | BUSINESS REGULATION HOTEL & RESTURANT |
| | DIVISION FOR REVIEW PRIOR TO RESUBMITT- |
| | ING FOR REVIEW. PLANS SHALL BE STAMPED |
| | AND WORKSHEETS FROM DBPR ATTACHED TO |
| | EACH SET OF PLANS. SEC. 101.4.7 |
| | 2) CONTACT RODNEY COMPO, ENVIRONMENTAL |
| | COMPLIANCE FOR SIZING OF GREASE INTER- |
| | CEPTOR. WASTE ORD. #2938-96. (561) 837- |
| | 4074. |
| | 3) SEPARATE PERMITS REQUIRED FOR GAS, |
| | IRRIGATION, AND GREASE INTERCEPTOR. |
| | 4) SHT C-4.0 NO CONNECTION TO FLOOR |
| | DRAIN FOR THE REFUSE ENCLOSURE IS SHOWN. |
| | THIS SHALL BE TIED INTO THE GREASE LINE. |
| | 5) SHTS A-1.7 & P-2 NOTE STATES "CONDEN- |
| | SATE TO MOP SINK BELOW". THIS IS NOT |
| | APPROVED. CONDENSATE SHALL DRAIN SEPAR- |
| | ATELY OUT OF THE BLDG. TO A CATCH BASIN, |
| | A STORM LINE, OR APPROVED DRYWELL MIN. |
| | 1' FROM STRUCTURAL SIDEWALL. CITY CODE |
| | SECTION 90-125(5). |
| | 6) SHT P-2 CONDENSATE LINE FOR FREEZER/ |
| | COOLER. A SEPARATE TRAP REQUIRED FOR |
| | EACH UNIT AND NO DOUBLE TRAPPING. SEC |
| | 1002.1 - TRAP OUTSIDE COOLER TO BE RE- |
| | MOVED. |
| | 7) SHT P-2 KEY NOTES #3, FLOOR DRAIN NOT |
| | AN APPROVED INDIRECT WASTE INTERCEPTOR. |
| | SEE SECTIONS 802.3 & 802.3.2, FLOOR SINK |
| | OR HUB DRAIN REQUIRED. |
| | 8) SHT P-4 MORE INFORMATION ON PIPE SUP- |
| | PORT ON ROOF REQUIRED. INDICATE HOW SUP- |
| | PORTS WILL BE FASTENED TO THE ROOF. SHOW |
| | HOW SUPPORTS WILL BE ABLE TO WITHSTAND |
| | THE 140 MPH WIND LOADS. |
| | 9) SHT P-5 WATER RISER DIAGRAM, WATER |
| | HAMMER ARRESTORS SHALL BE LOCATED NEAR |
| | THE FIXTURES IN AN "EFFECTIVE RANGE" NOT |
| | IN THE CEILING AS SHOWN. PDI-WH 201 AND |
| | MANUF. INSTALL. INSTRUCTIONS. - BALL |
| | CHECKS AT MOP SINK AND CAN WASH SHALL BE |
| | ACCESSIBLE. |
| | 10) P-6 FIXTURE CONNECTION SHEDULE #36 |
| | CATALOG INDICATES D50-064 IS A FLOOR |
| | DRAIN WHICH IS NOT AN APPROVED INDIRECT |
| | WASTE RECEPTOR. SEC 802.3 & 802.3.2. |
| | 11) WATER FILTER SHALL BE NSF APPROVED |
| | PER SECTION 611.1. SUBMIT MANUF. SPECI- |
| | FICATION SHEETS. |
| | 12) SHT P-7 PLUMBING SPECIFICATIONS PART |
| | 3 - #7 PIPING SUPPORT SHALL BE PER TABLE |
| | 308.5. |
| | 13) SUBMIT CALCULATIONS FOR PRIMARY AND |
| | SECONDARY ROOF DRAINS PER SECTIONS 1106 |
| | AND 1107 AND ALL ALL SUBSECTIONS. SHOW |
| | SQUARE FOOTAGE OF ROOF AND SHOW 1/2 AREA |
| | OF ALL VERTICAL WALLS INCLUDING PARAPETS |
| | BEING ADDED TO ROOF S.F. |
| | 14) RAIN WATER SHALL DISCHARGE A MINIMUM |
| | OF 1 FOOR FROM THE SIDE WALL OF THE |
| | STRUCTURE PER SECTION 1503.4.4 |
| | 15) THE FOLLOWING INFORMATION IS REQUIR- |
| | ED FOR GAS PERMIT, |
| | A. SUBMIT AN ISOMETRIC DRAWING THAT |
| | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE |
| | AND CORRESPONDING LENGTHS PER FBC-2001 |
| | FUEL GAS CODE. |
| | B. SHOW THE DISTANCE FROM THE POINT OF |
| | DELIVERY, (METER), TO THE MOST REMOTE |
| | OUTLET IN THE BUILDING AND/OR SYSTEM PER |
| | FBC-2001 FUEL GAS CODE APPENDIX A - USE |
| | OF CAPACITY TABLES (A)(3). |
| | C. INDICATE THE DELIVERY PRESSURE (PSI) |
| | PER FBC-2001 FUEL GAS CODE SEC. 402.2. |
| | NATURAL GAS SPECIFY .5 PSI OR 2 PSI. |
| | MINIMUM 1/2 LB SYSTEM SUPPLIED. |
| | D. SUBMIT MANUFACTURE SHEETS FOR ALL GAS |
| | EQUIPMENT TO VERIFY COMPLIANCE WITH |
| | STANDARDS NFPA 54, NFPA 58, AND THE |
| | FBC-2001 FUEL GAS CODE SEC 402.2 |
| | **************************************** |
| | A PROFESSIONAL ENGINEER SHALL SIGN HIS |
| | NAME AND AFFIX HIS SEAL TO ALL PLANS, |
| | SPECIFICATIONS, REPORTS AND FINAL BID |
| | DOCUMENTS PROVIDED TO THE OWNER OR THE |
| | OWNER'S REPRESENTATIVE, OR OTHER DOCU- |
| | MENTS PREPARED OR ISSUED BY SAID REGIS- |
| | TRANT AND BEING FILED FOR PUBLIC RECORD. |
| | THE DATE THAT THE SIGNATURE AND SEAL IS |
| | AFFIXED AS PROVIDED HEREIN SHALL BE EN- |
| | TERED ON SAID PLANS, SPECIFICATIONS, RE- |
| | PORTS, OR OTHER DOCUMENTS IMMEDIATELY |
| | UNDER THE SIGNATURE OF THE PROFESSIONAL |
| | ENGINEER, FAC 61G15-23.002(1) |
| | FS 471.025 |
| | EACH SHEET OF PLANS AND PRINTS WHICH |
| | MUST BE SEALED UNDER THE PROVISIONS OF |
| | CHAPTER 471 SHALL BE SEALED, SIGNED AND |
| | DATED BY THE PROFESSIONAL ENGINEER IN |
| | RESPONSIBLE CHARGE. FAC 61G15-23.002(2) |
| | FS 471.025 |
| | ENGINEERS SHALL LEGIBLY INDICATE THEIR |
| | NAME, ADDRESS AND LICENSE NUMBER ON EACH |
| | SHEET. IF PRACTICING THROUGH A DULY |
| | AUTHORIZED ENGINEERING BUSINESS, ENGIN- |
| | EERS, ENGINEERS SHALL LEGIBLY INDICATE |
| | THEIR NAME AND LICENSE NUMBER, AS WELL |
| | AS, THE NAME, ADDRESS AND CERTIFICATE OF |
| | AUTHORIZATION NUMBER OF THE ENGINEERING |
| | BUSINESS ON EACH SHEET. A TITLE BLOCK |
| | WILL SATISFY THIS REQUIREMENT. FAC |
| | 61G15-23.002(2) - FS 471.025 |
| | **************************************** |
| | <<<<<<<<>>>>>>> |
| | PLEASE CLEARLY INDICATE THE REVISION AND |
| | REMOVE AND REPLACE ANY PAGES AS NECESS- |
| | ARY. SUBMIT (1) SET OF OLD DRAWINGS WITH |
| | THE PLANS WHEN RESUBMITTING PLANS. A |
| | TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR |
| | SPECIFICATION PAGE WHERE THE CHANGES CAN |
| | BE FOUND, WILL HELP TO EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |