2004-05-12 00:00:00DENIED:
 1.ADDITIONAL PERMITS REQUIRED FOR THE
 HOOD, FIRE SUPPRESSION AND WALK-IN
 COOLERS.PROVIDE MANUFACTURER
 SUBMITTAL & INSTALLATION INSTRUCTIONS
 FOR THE WALK-IN COOLERS WITH PERMIT
 APPLICATION.SHOULD CONDENSORS BE
 REMOTE, PROVIDE MANUFACTURER SUBMITTAL
 FOR THE ROOF STANDS.
  
 2.PLAN SHEETS M-1 & M-2 INDICATE
 EXHAUST FROM HOOD SHALL BE 10 FT FROM
 PARAPETS.PER 2001 FBC(M) 506.3.14.3,
 OUTLETS SHALL BE NOT LESS FROM PROPERTY
 LINES & FRESH AIR INTAKES.
  
 3.PLAN SHEET M-2 INDICATES 3M FIRE
 BARRIER WRAP 15A, PROVIDE MANUFAUCTURER
 INSTALLATION INSTRUCTIONS ON THE
 JOBSITE AT THE TIME OF INSPECTION.DO
 NOT COVER WELDS TO GREASE DUCT PRIOR TO
 INSPECTION.
  
 4.PLAN SHEET M-3 DETAIL #5, NOTE
 INDICATES FACTORY INSTALLED DUCT SMOKE
 DETECTORS ARE TO BE RELOCATED FROM THE
 SUPPLYTO THE RETURN.PER 2001 FBC(M)
 606.2.1, DUCT SMOKE DETECTORS SHALL BE
 INSTALLED IN THE SUPPLY AIR SYSTEM.
  
 5.PLEASE PROVIDE OUTSIDE AIR
 CALCULATIONS PER 2001 FBC(M) 403.3.
  
 6.PLAN SHEET M-3 DETAIL 7, PLEASE NOTE
 PER 2001 FBC 1511.7 CURB HEIGHT FOR THE
 RTU SHALL BE NO LESS THAN 8" ABOVE THE
 ROOF SURFACE.
  