| 2004-05-12 00:00:00 | DENIED: |
| | 1.ADDITIONAL PERMITS REQUIRED FOR THE |
| | HOOD, FIRE SUPPRESSION AND WALK-IN |
| | COOLERS.PROVIDE MANUFACTURER |
| | SUBMITTAL & INSTALLATION INSTRUCTIONS |
| | FOR THE WALK-IN COOLERS WITH PERMIT |
| | APPLICATION.SHOULD CONDENSORS BE |
| | REMOTE, PROVIDE MANUFACTURER SUBMITTAL |
| | FOR THE ROOF STANDS. |
| | |
| | 2.PLAN SHEETS M-1 & M-2 INDICATE |
| | EXHAUST FROM HOOD SHALL BE 10 FT FROM |
| | PARAPETS.PER 2001 FBC(M) 506.3.14.3, |
| | OUTLETS SHALL BE NOT LESS FROM PROPERTY |
| | LINES & FRESH AIR INTAKES. |
| | |
| | 3.PLAN SHEET M-2 INDICATES 3M FIRE |
| | BARRIER WRAP 15A, PROVIDE MANUFAUCTURER |
| | INSTALLATION INSTRUCTIONS ON THE |
| | JOBSITE AT THE TIME OF INSPECTION.DO |
| | NOT COVER WELDS TO GREASE DUCT PRIOR TO |
| | INSPECTION. |
| | |
| | 4.PLAN SHEET M-3 DETAIL #5, NOTE |
| | INDICATES FACTORY INSTALLED DUCT SMOKE |
| | DETECTORS ARE TO BE RELOCATED FROM THE |
| | SUPPLYTO THE RETURN.PER 2001 FBC(M) |
| | 606.2.1, DUCT SMOKE DETECTORS SHALL BE |
| | INSTALLED IN THE SUPPLY AIR SYSTEM. |
| | |
| | 5.PLEASE PROVIDE OUTSIDE AIR |
| | CALCULATIONS PER 2001 FBC(M) 403.3. |
| | |
| | 6.PLAN SHEET M-3 DETAIL 7, PLEASE NOTE |
| | PER 2001 FBC 1511.7 CURB HEIGHT FOR THE |
| | RTU SHALL BE NO LESS THAN 8" ABOVE THE |
| | ROOF SURFACE. |
| | |