| Date |
Text |
| 2004-04-29 00:00:00 | 1) DEMOLITION, RENOVATION AND |
| | CONSTRUCTION TO COMPLY WITH NFPA 241. |
| | |
| | 2) THE PLANS INDICATE TYPE VI |
| | CONSTRUCTION BEING PROPOSED. TYPE VI |
| | CONSTRUCTION IS NOT PERMITTED IN THE |
| | CITY FIRE LIMITS. SINCE THE LOCATION |
| | IS WITHIN THE CITY FIRE LIMITS CERTAIN |
| | RESTRICTIONS WILL APPLY. PLEASE SEE |
| | APPENDIX F LOCAL AMENDMENTS TO THE |
| | FLORIDA BUILDING CODE. PLEASE REVISE |
| | PLANS AS REQUIRED. |
| | |
| | 3) MORE DETAILS REQUIRED ON HIRING |
| | TRAILER. AGAIN TYPE VI CONSTRUCTION |
| | IS NOT ALLOWED IN THE FIRE LIMITS. |
| | ONLY TRAILERS ASSOCIATED WITH |
| | CONSTRUCTION ACTIVITIES ARE ALLOWED |
| | TO BE TYPE VI. |
| | |
| | 4) WRONG BUILDING ADDRESS NOTED ON |
| | TILE PAGE. |
| | |
| | 5) SEPARATE PLANS AND PERMITS |
| | REQUIRED FOR ALL HOOD, DUCT, AND |
| | FIRE SUPPRESSION SYSTEMS. |
| | |
| | 6) PLEASE INDICATE INTERIOR FINSH |
| | CLASSIFICATION FOR WALLS AND CEILINGS. |
| | |
| | 7) PLEASE PROVIDE PRODUCT DATA ON |
| | KITCHEN HOOD DUCT WRAP. |
| | |
| | 8) PLEASE ADVISE LOCATIONS OF PFE'S. |
| | |
| | 9) FIRE LIMITS-ROOF COVERING SHALL |
| | BE CLASS A OR B. |
| | |
| | 10) BUILDING ADDRESS REQUIRED. MINIMUM |
| | 6" HIGH NUMBERS THAT CONTRAST ARE |
| | REQUIRED. |
| | |
| | MIKE CARSILLO, ASSISTANT FIRE MARSHAL |
| | 835-2910 |