Plan Review Notes
Plan Review Notes For Permit 04041900
Permit Number 04041900
Review Stop E
Sequence Number 1
Notes
Date Text
2004-05-08 00:00:00************** UNSAT *****************
  
 1)NOTE: PLEASE SEE FAC 61G15-23.002 FOR
 ALL INFORMATION REQ'D ON TITLE BLOCK.
 PLEASE ALSO SEE FS 471.023 FOR REQ'D
 CA LICENSE #.
 THIS IS REQ'D FOR ALL TRADES WEATHER OR
 NOTE COMMENT IS MADE BYOTHER REVIEWER.
  
 2)NOTE: PLEASE SUBMIT/SHOW WIND LOAD FOR
 ANY PARKING LOT LT FIXTURES AND POLES.
 FBC 140 MPH..
 COULD NOT BE LOCATED ON ES-1.0,2.0 OR
 E1-1.
  
 3)NOTE: PLEASE CLARIFY MANUAL MEANS OF
 DISCONNECT FOR SHUNT TRIP BRKRS IN
 MDP IN THE EVENT OF SHUNT TRIP FAILURE.
 230.76,230.79
  
 4)NOTE: PLEASE SEE E-6.1, SHOWS LOADS
 SUMMARYS REFERENCING 1996/1999 NEC
 PLEASE SEE THAT WE NOW UNDER THE 2002
 NEC WHICH WAS ADOPTED BY THE STATE ON
 7/1/2003
 ALL GFI PROTECTION WILL BE REQ'D UNDER
 2002 NEC.
  
 5)NOTE: PLEASE INCLUDE/SHOW WINDOW
 RECEPTS WILL BE REQ'D PER 210.62
  
 PLEASE NOTE: PLANS ARE ONLY IN FOR
 PLAN REVIEW AND NOT FOR PERMIT.
  
 PLEASE REMOVE ALL OLD/ VOIDED SHEEST
 AND ONLY INSERT NEW SHEETS INTO COMPLETE
 SETS FOR REVIEW AND STAMPING. ONE SET
 OF OLD MAY BE SUBITTED FOR REFERENCE
 REQ'D BY SOME REVIEWERS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]


Account Summary | Usage Policy | Privacy Policy