| 2004-05-08 00:00:00 | ************** UNSAT ***************** |
| | |
| | 1)NOTE: PLEASE SEE FAC 61G15-23.002 FOR |
| | ALL INFORMATION REQ'D ON TITLE BLOCK. |
| | PLEASE ALSO SEE FS 471.023 FOR REQ'D |
| | CA LICENSE #. |
| | THIS IS REQ'D FOR ALL TRADES WEATHER OR |
| | NOTE COMMENT IS MADE BYOTHER REVIEWER. |
| | |
| | 2)NOTE: PLEASE SUBMIT/SHOW WIND LOAD FOR |
| | ANY PARKING LOT LT FIXTURES AND POLES. |
| | FBC 140 MPH.. |
| | COULD NOT BE LOCATED ON ES-1.0,2.0 OR |
| | E1-1. |
| | |
| | 3)NOTE: PLEASE CLARIFY MANUAL MEANS OF |
| | DISCONNECT FOR SHUNT TRIP BRKRS IN |
| | MDP IN THE EVENT OF SHUNT TRIP FAILURE. |
| | 230.76,230.79 |
| | |
| | 4)NOTE: PLEASE SEE E-6.1, SHOWS LOADS |
| | SUMMARYS REFERENCING 1996/1999 NEC |
| | PLEASE SEE THAT WE NOW UNDER THE 2002 |
| | NEC WHICH WAS ADOPTED BY THE STATE ON |
| | 7/1/2003 |
| | ALL GFI PROTECTION WILL BE REQ'D UNDER |
| | 2002 NEC. |
| | |
| | 5)NOTE: PLEASE INCLUDE/SHOW WINDOW |
| | RECEPTS WILL BE REQ'D PER 210.62 |
| | |
| | PLEASE NOTE: PLANS ARE ONLY IN FOR |
| | PLAN REVIEW AND NOT FOR PERMIT. |
| | |
| | PLEASE REMOVE ALL OLD/ VOIDED SHEEST |
| | AND ONLY INSERT NEW SHEETS INTO COMPLETE |
| | SETS FOR REVIEW AND STAMPING. ONE SET |
| | OF OLD MAY BE SUBITTED FOR REFERENCE |
| | REQ'D BY SOME REVIEWERS. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |