| Plan Review Notes For Permit 04041895 |
| Permit Number |
04041895 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2004-05-14 00:00:00 | DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | FBC-2001 BUILDING | | | FBC-2001 CHAPTER 11 | | | | | | 1) SHT A1.2 A DRINKING FOUNTAIN IS REQ- | | | UIRED PER TABLE 403.1. ALSO SEE SECTION | | | 410.1 | | | 2) SHT A1.2 SINKS SHALL COMPLY WITH SEC. | | | 11-4.24 AND ALL SUBSECTIONS. SHOW CLEAR | | | FLOOR SPACE, HEIGHT, KNEE CLEARANCE, EX- | | | POSED PIPES AND SURFACES ECT. | | | 3) SHT P-1 FLOOR DRAINS ARE NOT APPROVED | | | FOR INDIRECT WASTE. SEE SECTIONS 802.3 | | | AND 802.3.2. | | | 4) SHT P-1 SUBMIT CALCULATIONS FOR POINT | | | LOADING OF BOTTON CHORD OF THE BAR JOIST | | | AT WATER HEATER. INDICATE WHERE THE LOAD | | | IS BEING TRANSFERRED TO. SECTION 1614.2. | | | 1. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] |
|