| 2004-05-17 00:00:00 | BUILDING PLAN REVIEW |
| | PERMIT: 04041895 |
| | ADD: 222 LAKEVIEW AV |
| | CONT: HEDRICK BROTHERS |
| | TEL: (561)718-8341 |
| | FL BLD CODE= 2001 FLORIDA BUILDING CODE |
| | |
| | 1ST REVIEW |
| | ACTION: DENIED |
| | |
| | 1) SHEETSA1.3 INDICATE VARIOUS SOFFITS |
| | BUT NO DETAIL AS TO WHAT MATERIAL THEY |
| | SOFFITS ARE FASTENED TO NOR THE FASTENER |
| | |
| | 2) DOOR# 1 DOES NOT INDICATE WHAT THE |
| | FIRE RATING IS PROVIDE IF FOR EXISTING |
| | DOORS? |
| | |
| | 3) DOOR #18 & 19 DO NOT PROVIDE WHAT THE |
| | FIRE RESISTANCE RATING IS? |
| | |
| | 4) TABLE 803.3 MINIMUM INTERIOR FINISH |
| | CLASSIFICATION; PROVIDE INFORMATION |
| | BASED ON INTERIOR FINISH REQUIREMENTS |
| | BASED ON OCCUPANCY |
| | |
| | 5)704.2.1.4 CORRIDOR PARTITIONS, SMOKE |
| | STOP PARTITIONS, HORIZONTAL EXIT PART- |
| | ITIONS, EXIT ENCLOSURES, AND FIRE |
| | RATED WALLS REQUIRED TO HAVE PROTECTED |
| | OPENINGS SHALL BE EFFECTIVELY AND |
| | PERMANETLY IDENTIFIED WITH SIGNS OR |
| | STENCILING IN A MANNER ACCEPTABLE TO THE |
| | AUTHORITY HAVING JURISDICTION. SUCH IDEN |
| | TIFICATION SHALL BE ABOVE ANY DECORATIVE |
| | CEILING CEILING AND IN CONCEALED SPACES. |
| | SUGGESTED WORDING" FIRE & SMOKE BARRIER |
| | PROTECT ALL OPENINGS". |
| | |
| | 6) TYPE I/ II BUILDINGS WOOD IN PARTI- |
| | TIONS BLOCKING, BACKING MUST BE FIRE |
| | RETARDANT TREATED WOOD, 609.1.2. |
| | |
| | 7) KITHEN ELEVATION, 11-4.24.4 SINK |
| | HEIGHT. SINKS SHALL BE MOUNTED WITH THE |
| | COUNTER OR RIM NO HIGHER THAN 34INCHES. |
| | |
| | 8) PROVIDE FIRE SPRINKLER PLANS. |
| | |
| | BUILDING PLAN REVIEW |
| | JIM WITMER |
| | TEL: (561)805-6715 |
| | FAX: (561)659-8026 |