Plan Review Notes
Plan Review Notes For Permit 04041894
Permit Number 04041894
Review Stop E
Sequence Number 1
Notes
Date Text
2004-05-18 00:00:00************ UNSAT *************
  
 1)NOTE: PLEASE CORRELATE LOAD PLANS/
 MOTORS AND HEAT PUMP WITH LOAD CALCULAT-
 -IONS.
 PLEASE SEE LOAD SHOWN FOR HEAT PUMP
 DOES NOT CORRELATE WITH HEAT PUMP SPECS.
 PLEASE CIRCLE HEAT PUMP TO BE INSTALLED.
  
 PLEASE SEE PLANS SHOW A 3HP POOL PUMP,
 PLEASE SEE NEC 430 TABLES FOR LOAD OF
 3HP/230V PUMP.
  
 PLEASE SEE A BLOWER IS INCLUDED ON PLANS
 HOWEVER, THIS IS NOT IN LOAD CALCS?
  
 PLEASE SEE ALL CONTINUOUS LOADS(3 OR
 MORE HRS) IS TO BE FIGURED AT 125%.
 230.42,215.3,220.19 ETC.
  
 PLEASE RECONFIGURELOAD CALCUALTIONS.
  
 2)NOTE: PLEASE SEE FBC 104.2.1, ADDITION
 -AL ELECTRICAL LOAD CALCS SHALL CONTAIN
 A PRINTED NAME AND SIGNATURE OF THE
 PERSON RESPONSIBLE FOR PLANS.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  