| 2004-05-18 00:00:00 | ************ UNSAT ************* | | | | | | 1)NOTE: PLEASE CORRELATE LOAD PLANS/ | | | MOTORS AND HEAT PUMP WITH LOAD CALCULAT- | | | -IONS. | | | PLEASE SEE LOAD SHOWN FOR HEAT PUMP | | | DOES NOT CORRELATE WITH HEAT PUMP SPECS. | | | PLEASE CIRCLE HEAT PUMP TO BE INSTALLED. | | | | | | PLEASE SEE PLANS SHOW A 3HP POOL PUMP, | | | PLEASE SEE NEC 430 TABLES FOR LOAD OF | | | 3HP/230V PUMP. | | | | | | PLEASE SEE A BLOWER IS INCLUDED ON PLANS | | | HOWEVER, THIS IS NOT IN LOAD CALCS? | | | | | | PLEASE SEE ALL CONTINUOUS LOADS(3 OR | | | MORE HRS) IS TO BE FIGURED AT 125%. | | | 230.42,215.3,220.19 ETC. | | | | | | PLEASE RECONFIGURELOAD CALCUALTIONS. | | | | | | 2)NOTE: PLEASE SEE FBC 104.2.1, ADDITION | | | -AL ELECTRICAL LOAD CALCS SHALL CONTAIN | | | A PRINTED NAME AND SIGNATURE OF THE | | | PERSON RESPONSIBLE FOR PLANS. | | | | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE TO CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CITY OF WEST PALM BEACH | | | CONSTUCTION SERVICES DEPT. | | | 561-805-6717 | | | [email protected] |
|