Plan Review Notes
Plan Review Notes For Permit 04041812
Permit Number 04041812
Review Stop E
Sequence Number 2
Notes
Date Text
2004-06-23 00:00:00************ PROVISO/ REVISION ******
  
 1 )NOTE: PLEASE SEE 220.3B4.
 PLEASE SHOW ALL RECESSED LTS BASED ON
 MAX WATTAGE FOR FIXTURE(S). THIS MAY NOT
 BE FIGURED IN W/ 3W/PER SQ FT.
 PLEASE PROVIDE FIXTURE INFORMATION ON
 LEGEND.
 PLEASE REVISE PLANS TO SHOW ACTUAL
 INSTALLATION. PLANS SHOW "OPTS" FOR
 MANY RECESSED LTS.
  
 PLEASE SUBMIT REVISED PLANS BEFORE
 ROUGH ELECTRICAL INSPECTION.
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  