| 2004-05-06 00:00:00 | ******** REDLINED/ PROVSIO ********* | | | | | | 1)NOTE : LOAD FOR RANGE TO BE A MIN OF | | | 8KW PER 220.19 | | | | | | 2)NOTE: MAX LOAD FOR A 1P20A CIRCUIT IS | | | 1.9KW. IRRG PUMP, WASHER SHOWN AT 2KW. | | | | | | SD'S TO BE INSTALLED PER NFPA-72 8-1.4.2 | | | | | | | | | REVISE PLANS BEFORE ROUGH. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 |
|