| Plan Review Notes For Permit 04041733 |
| Permit Number |
04041733 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2004-05-04 00:00:00 | ******** REDLINED /PROVISO ******* | | | | | | REVISE PLANS BEFORE ROUGH. | | | | | | 1)NOTE: LOAD CALCUALTIONS TO REFLECT | | | A MIN OF 8KW FOR RANGE PER 220.19 | | | | | | 2)NOTE IRRG PUMP, WASHER SHOWN EXCEEDING | | | MAX LOAD OF 1.9KW ON A 1-P20A CIRCUIT. | | | | | | SD'S NOTED TO BE INSTALLED PER NFPA-72 | | | 8-1.4.2 | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE TO CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CITY OF WEST PALM BEACH | | | CONSTUCTION SERVICES DEPT. | | | 561-805-6717 | | | [email protected] |
|