| Plan Review Notes For Permit 04041726 |
| Permit Number |
04041726 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2004-07-21 00:00:00 | 1-DETAIL E/4 AND RESIDENTIAL NOTES ON | | | DRAWINGS #2 DON'T MATCH. CLARIFY | | | FASTENER SPACING. SECTION 104.2.1.2 | | | CITY AMENDMENTS TO FBC 2001. | | | 2-SECTION A4: SPECIFY WHERE ARE TABLES | | | 6 AND 8 FOR ROOF FASTENERS TAKEN FROM? | | | SEC. 104.2.1.1 CITY AMENDEMNTS TO FBC | | | 3-PROVIDE COPIES OF GARAGE DOOR DRAWINGS | | | SUBMITTED TO SBCCI FOR APPROVAL. NEED | | | DRAWINGS SIGNED AND SEALED ON DATE | | | NOTED ON SBCCI EVALUATION REPORT. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CALL | | | JULIO GOMEZ AT 805-6712. |
|