| Plan Review Notes For Permit 04041726 |
| Permit Number |
04041726 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2004-05-21 00:00:00 | BUILDING REVIEW PROVISO: | | | 1-DETAIL E/4 AND RESIDENTIAL NOTES ON | | | SHEET #2 DON'T MATCH. CLARIFY FASTENER | | | SPACING. SEC 104.2.1.2 CITY AMENDMENTS | | | TO FBC 2001. | | | 2-SECTION A/4: SPECIFY WHERE ARE TABLES | | | 6 AND 8 FOR ROOF TILE FASTENING TAKEN | | | FROM. SEC 104.2.1.1 CITY AMENDMENTS | | | TO FBC 2001. | | | 3-PROVIDE COPIES OF GARAGE DOOR DWGS | | | THAT WERE SUBMITTED TO SBCCI FOR | | | APPROVAL. NEED DWGS THAT WERE SIGNED | | | AND SEALED ON DATE NOTED ON SBCCI | | | EVALUATION REPORT. | | | 4-FLOOD ZONE AO: WILL NEED TO PROVIDE | | | THE ELEVATION CERTIFICATE. |
|