| Plan Review Notes For Permit 04041648 |
| Permit Number |
04041648 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2004-05-03 00:00:00 | ******** REDLINED/ PROVISO******* | | | | | | REVISE PLANS BEFORE ROUGH. | | | | | | 1)NOTE: PLEASE SEE MIN LOAD FIGURED FOR | | | RANGE TO BE 8KW PER 220.19. SHOWN AS | | | 7.5KW | | | | | | 2)NOTE: MAX LOAD FOR 1-P 20A CIRCUITS | | | 1.9KW,80% IRRG PUMP,WASHER ARE SHOWN AS | | | 2KW | | | | | | SD'S PER NFPA-72 8-1.4.2 | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE TO CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CITY OF WEST PALM BEACH | | | CONSTUCTION SERVICES DEPT. | | | 561-805-6717 | | | [email protected] |
|